Starting up for the first time
67
P208
FRT limit ++
P208: 30%
Only enabled if parameter P270 combustion chamber
temperature control is activated. If the combustion chamber
temperature does not reach the setpoint, the duration for
the burner auger switching on is increased by a maximum
of this percentage.
yes
30
P209
FRT limit – –
P209: 80%
Only enabled if parameter P270 combustion chamber
temperature control is activated. If the combustion chamber
temperature exceeds the setpoint, the duration for the
burner auger switching on is reduced by a maximum of
this percentage.
yes
80
P210
Cap. hopper active
P210: 1
Here you can activate the capacitive sensor for the hopper
on the suction system. If an auger with textile tank with
oscillating floor is implemented, the capacitive sensor for
the hopper is located on the excentric motor.
yes
1
P211
Cap. RA active
P211: 0
Kap RA is always active at auger systems
yes
1
P212
Ash box
P212: 0
Here you can activate the de-ashing system. If Parameter
212 is active, Parameter 213 is not displayed. If you have
also an burner plate deashing system (optional for PE(S)
12–32) it runs with the de-ashing system.
0 = inactive, 1 = active
Note:
Does not start the boiler more than five days, on
Friday 12.00 a.m. the de-ashing system runs for
3/5 minutes.
yes
0/0/1
P213
Deashing
P213: 0
Here you can activate the burner plate deashing system
0 = inactive, 1 = active
If Parameter 213 is active, Parameter 212 is not displayed
yes
0
P214
Neg. draft Min
P214: 32EH
If the negative draft inside the combustion chamber falls
below the minimum value for longer than 1 Minute (P217),
the system switches to fault mode. Value = 0 negative draft
supervision inactive. (Displayed only with negative draft
measuring connected)
yes
32/32/45
P215
Neg. draft Max
P215: 300EH
Maximum negative draft in combustion chamber. If this
is exceeded for longer than 1 minute (P217), the system
switches to fault mode. (Displayed only with negative draft
measuring connected)
yes
300
P216
Neg. draft scrubber
P216: 35EH
Min. negative draft of scrubber system only on condensing
boiler systems. If the value falls below the minimum
negative draft then the system switches to fault mode. If a
value below 10 is set, the scrubber switches on according
to the value set in P 193 and P 194.
yes
35
P217
Neg. draft time
P217: 60s
If the negative draft inside the combustion chamber
falls below the minimum value for longer than the set
supervision time, the system goes to fault mode and
displays "Negative draft".
yes
60
P218
Neg. draft setpoint
P218: 60EH
If the negative draft in the combustion chamber falls below
the setpoint, the speed of the flue gas fan is increased. If
the negative draft increases then the speed of the flue gas
fan is reduced again. Value = 0, negative draft supervision
inactive. (Displayed only with negative draft measuring
connected)
yes
60
PE 3671 USA 2.3
Installation Manual PES 36–56
Содержание Pellematic PES 12-20
Страница 38: ...Connecting up to the power supply 38 Installation Manual PES 36 56 PE 3671 USA 2 3...
Страница 46: ...Connecting up to the power supply 46 Installation Manual PES 36 56 PE 3671 USA 2 3...
Страница 47: ...Connecting up to the power supply 47 PE 3671 USA 2 3 Installation Manual PES 36 56...
Страница 52: ...Operating the pellet boiler 52 Setting date and time Installation Manual PES 36 56 PE 3671 USA 2 3...
Страница 88: ...Appendix 88 Installation Manual PES 36 56 PE 3671 USA 2 3...
Страница 92: ...Appendix 92 Installation Manual PES 36 56 PE 3671 USA 2 3...
Страница 99: ...Appendix 99 Labeling 105x74 PE 3671 USA 2 3 Installation Manual PES 36 56...
Страница 100: ......