Starting up for the first time
69
P236
CF Logger
P236: 0
Activates the data logger on the CF card. This can only
be activated if a CF card is located in the relevant socket.
Display:
• -1 – no CF card in socket 0 CF card in socket, logger
not active
• 1 – CF card in socket and logger program is running
Records the current status and malfunctions of KT, RGT,
FRT, ES, PA, LL, SZ, UP providing sensors are connected.
(Displays parameters only with CF card)
yes
0
P237
Sample time
P237: 60s
The recording interval of the data archive in seconds
(displays parameters only with CF card)
yes
60
P238
Param. -> CF
P238: 0
Outputs the current parameter values of the CF card. The
file name is the 5-figure PLC number (Pxxxxx_0.csv). This
is marked on the label in the CF socket. (Display only with
CF card inserted)
yes
0
P239
CF -> Param.
P239: 0
Damage to property
Do not change the format of the output file from
"Startkennung &&&" onwards. You may only change
the numerical values. Do not enter any new lines,
no semi-colons, spaces or other characters. The
values are checked for plausibility, not for parameter
numbers. (Display only with CF card inserted)
Reads in the parameter values from the CF card. The file
name must be the 5-figure PLC number (Pxxxxx_0.csv).
This is marked on the label in the CF socket and in
parameter P101. The best method is to write data to the
CF card using P238 – then edit the export file in Excel or a
text editor and then read the data in again. You can insert
comments such as the customers name and any special
lines of code in front of the text "Startkennung &&&" .
Exception: you cannot use "&"
yes
0
P242
Enable and disable the outdoor sensor with parameter
P242
PT1000 outdoor sensor at the place of the PT1000 RGF
Sensor Input at:
-Outside temp. . >59°F set value P263: 158°F Stop temp.
P202: P263+11°F
–41°F < Outside temp. <=59°F set value P263: 176°F Stop
temp. P202: P263+11°F
–32°F < Outside temp. <=41°F set value P263: 183°F Stop
temp. P202: P263+11°F
–14°F < Outside temp. <=32°F set value P263: 183°F Stop
temp. P202: P263+11°F
—Outside temp. <14°F set value P263: 192°F Stop temp.
P202: P263+11°F
The parameter Boiler Set t + + / P264 (= correction factor to
control temperature), serves to change additionally the set
value in the range of +10 to -9 ° (move temperature curve)
for example: outside temp. = 28 ° F and parameter P264
+2 ° F
set value= 185°F (183°F+2°F)
PE 3671 USA 2.3
Installation Manual PES 36–56
Содержание Pellematic PES 12-20
Страница 38: ...Connecting up to the power supply 38 Installation Manual PES 36 56 PE 3671 USA 2 3...
Страница 46: ...Connecting up to the power supply 46 Installation Manual PES 36 56 PE 3671 USA 2 3...
Страница 47: ...Connecting up to the power supply 47 PE 3671 USA 2 3 Installation Manual PES 36 56...
Страница 52: ...Operating the pellet boiler 52 Setting date and time Installation Manual PES 36 56 PE 3671 USA 2 3...
Страница 88: ...Appendix 88 Installation Manual PES 36 56 PE 3671 USA 2 3...
Страница 92: ...Appendix 92 Installation Manual PES 36 56 PE 3671 USA 2 3...
Страница 99: ...Appendix 99 Labeling 105x74 PE 3671 USA 2 3 Installation Manual PES 36 56...
Страница 100: ......