Starting up for the first time
68
P221
Min. downtime
P221: 60m
The electronic ignition is not activated if the burner attempts
to start within the set duration after the last burner stop.
yes
60
P222
Auger dur. ign
P222: 50zs
Running duration of burner auger during the ignition phase,
specified in tenths of a second
yes
50
P223
Auger pause ign
P223: 20zs
Pause duration of burner auger during the ignition phase,
specified in tenths of a second
yes
20
P224
Fan rpm ign
P224: 100%
Speed of burner fan during ignition phase.
yes
100
P225
Suction ign
P225: 100%
Speed of flue gas fan during ignition phase.
yes
100
P226
Hyst. flue temp.
P226: 50°F
For ignition to take place successfully, the flue gas
temperature must exceed the boiler temperature by Hyst.
flue gas temperature.
yes
50
P228
Combustion ch. min.
P228: 248°F
Setpoint of combustion chamber temperature for successful
ignition.
Combustion chamber temperature 248°F, only when
combustion chamber sensor is active P270
yes
248
P229
Fan run on
P229: 420s
Minimum run on time (seconds) of burner fan after
switching off.
yes
420
P230
AGT++LL off
P230: 58°F
After the minimum run on time has expired, the combustion
air fan continues to run until the flue gas temperature is
lower than the boiler tempe the temperature value
set:
e.g.: boiler temperature = 169°F + 58°F = 227°F switch-off
temperature.
yes
58
P231
AGT++ SZ off
P231: 22°F
After the minimum run on time has expired, the flue gas fan
continues to run until the flue gas temperature is lower than
the boiler tempe the temperature value set:
e.g.: boiler temperature = 169°F + 22°F = 191°F switch-off
temperature.
yes
22
P233
P233: 0
Activation of the level detection system
1.....Level detection system using weighing cells for
FleXILO textile tanks.
2.....Level detection system using weighing cells at the
hopper for storage rooms.
3.....Level detection system using a capacitive sensor for
storage rooms and FleXilo textile tanks.
P234
P234: 0 kg
Displayed only, if P233 is 1.
Set the display of the current weight to 0 by putting in the
negative of the current weight shown in P 132. Therefore
you have to turn the thumbweel left.
P235
P235: 0 kg
Displayed only, if P233 is 2.
Set the display of the current weight to 0 by putting in the
negative of the current weight of the hopper shown in P
132. Therefore you have to turn the thumbweel left.
Installation Manual PES 36–56
PE 3671 USA 2.3
Содержание Pellematic PES 12-20
Страница 38: ...Connecting up to the power supply 38 Installation Manual PES 36 56 PE 3671 USA 2 3...
Страница 46: ...Connecting up to the power supply 46 Installation Manual PES 36 56 PE 3671 USA 2 3...
Страница 47: ...Connecting up to the power supply 47 PE 3671 USA 2 3 Installation Manual PES 36 56...
Страница 52: ...Operating the pellet boiler 52 Setting date and time Installation Manual PES 36 56 PE 3671 USA 2 3...
Страница 88: ...Appendix 88 Installation Manual PES 36 56 PE 3671 USA 2 3...
Страница 92: ...Appendix 92 Installation Manual PES 36 56 PE 3671 USA 2 3...
Страница 99: ...Appendix 99 Labeling 105x74 PE 3671 USA 2 3 Installation Manual PES 36 56...
Страница 100: ......