Installation Instructions
85002
│ Gas Valve 120Vrac VK4115
Revision Date: 2019-06-19
S:\NTI2001_N_Drive (1-20-09)\R&D\PARTS - ENGINEERING\Parts Department Stickers and Instructions\Current Parts Instructions (doc)\Parts
instructions word docs\85002 instructions - Gas Valve 120Vrac VK4115.doc
NTI Boilers Inc.
Tel: (506) 657-6000
Toll Free: 1-800-688-2575
Fax: 1-506-432-1135
Web: www.ntiboilers.com
Email: [email protected]
85002
Gas Valve 120Vrac VK4115
Applicable Appliance Models
Tx200, Tx200C
Kit Contents
85002 – Gas Valve
83134 – Regulator Adapter
Tools Required
Pipe Wrench (for gas line)
Adjustable Wrench (for gas line union)
5/16” Nut Driver
Phillips #2 and #1 Screwdriver
Flat Screwdriver
Torx T25 Screwdriver
Torx T40 Screwdriver
Combustion Analyzer
The installation of this gas valve must be performed by a qualified gas technician in accordance
with these instructions. Installing this valve without the proper background and training is
hazardous and may result in property damage serious injury or death.
Replacement Instructions
1)
Shut off the power and gas supply to the boiler.
2)
Remove the gas supply line from the gas valve.
3)
Remove the gas valve harness and feedback tube from the gas valve.
4)
Remove the screws securing the gas valve to the Venturi (T25) and remove the gas valve from the boiler.
5)
Transfer gas line inlet adapter to the new valve. Use care to ensure that the O-ring gasket does not fall out.
O-ring
–
Failure to properly re-intstall the gas line adapter O-ring will result in gas leakage
which may cause property damage, serious injury, or death.
6)
Transfer gas valve outlet gasket to the replacement gas valve.
Propane (LP):
if equipped with an LP orifice, reinstall
it in the outlet of the new gas valve (see Figure 2).
7)
Reinstall the new valve in the reverse order and perform the
Combustion Calibration Procedure
detailed on the
following pages.
Feedback Tube
–
Reconnect the tubing from the air-inlet to the gas valve feedback port.
Failure to properly reconnect the feedback tube will negate the boiler’s blocked vent safety
shutoff mechanizm, and could lead to incorrect combustion resulting in property damage,
serious injury or death.
Figure 1 Gas Valve
83134 Regulator
Adapter installed