![Manta MTS-1700 SERIES Скачать руководство пользователя страница 34](http://html1.mh-extra.com/html/manta/mts-1700-series/mts-1700-series_operation-and-reference-manual_1723616034.webp)
INTRODUCTION - Section 1
1-4 MTS-1700 SERIES OPERATION AND REFERENCE MANUAL
MANTA TEST SYSTEMS
CU A002 15A
1.4 TERMINOLOGY
The following section clarifies terminology defining various approaches to relay testing.
The MTS-1700 Series Universal Protective Relay Test System is very versatile, and may be used in all
these types of relay testing.
1.4.1 Static Relay Testing
Static relay testing refers to testing of relays using very slowly varying inputs to accurately locate pickup
points and to perform repeatable measurements.
1.4.2 Dynamic Relay Testing
This form of testing refers to testing of relays using instantaneous steps/ramping of voltage and current
inputs.
To closely simulate conditions during in-service operation, the voltages and currents are typically stepped
from a nominal level to a pre-determined fault level. The MTS-1710 has the unique ability to perform
dynamic testing under manual control.
1.4.3 Fault Playback
Fault playback refers to the regeneration of digitized voltage and current waveforms at high power levels.
The waveform data may originate from any of the following sources:
a) Fault records from digital fault recorders
b) Digital simulation output e.g. from Electromagnetic Transient Program (EMTP)
c) Event reports from microprocessor-based relays
d) User-defined waveforms
e) Fault record libraries
Playback of these waveforms allow actual and hypothetical fault events to be re-created. Analysis of
protective relay system performance can also be carried out as a result of these events. Real-time
simulation and analysis of system response to transients and other abnormal conditions is further
permitted.
For a more detailed discussion of this application, see the paper “Protective Relay Digital Fault Recording
and Analysis” by Elmo Price, Conference of Protective Relay Engineers, Texas A&M University, April,
1998.
1.4.4 On-Panel Testing
This refers to testing of relays and relay systems while they’re installed on panels and equipment racks.
This involves injecting voltages and currents directly to the panel to test complete system response, and to
verify correct input/output wiring and phasing.
Содержание MTS-1700 SERIES
Страница 30: ...TABLE OF CONTENTS xxx MTS 1700 SERIES OPERATION AND REFERENCE MANUAL MANTA TEST SYSTEMS CU A002 15A ...
Страница 38: ...INTRODUCTION Section 1 1 8 MTS 1700SERIESOPERATIONANDREFERENCEMANUAL MANTA TEST SYSTEMS CU A002 15A ...
Страница 44: ...SPECIFICATIONS Section 2 2 6 MTS 1700 SERIES OPERATION AND REFERENCE MANUAL MANTA TEST SYSTEMS CU A002 15A ...
Страница 248: ...FAULT PLAYBACK Section 7 7 12 MTS 1700 SERIES OPERATION AND REFERENCE MANUAL MANTA TEST SYSTEMS CU A002 15A ...
Страница 262: ...SERVICING Section 8 8 14 MTS 1700 SERIES OPERATION ANDREFERENCE MANUAL MANTA TEST SYSTEMS CU A002 15A ...
Страница 320: ...PROGRAMMABLE DIGITAL I O CHANNELS A 14 MTS 1700 SERIES OPERATION AND REFERENCE MANUAL MANTA TEST SYSTEMS CU A002 15A ...
Страница 340: ...E 4 MTS 1700 SERIES OPERATION AND REFERENCE MANUAL MANTA TEST SYSTEMS CU A002 15A ...
Страница 344: ...GLOSSARY F 4 MTS 1700 SERIES OPERATION AND REFERENCE MANUAL MANTA TEST SYSTEMS CU A002 15A ...