DETAILED OPERATION - Section 4
4-18
MTS-1700 SERIES OPERATION AND REFERENCE MANUAL
MANTA TEST SYSTEMS
CU A002 15A
FIGURE 4.12 PERCENTAGE DIFFERENTIAL RELAY TESTING
4.6.6
HARMONIC Current Mode
This current mode generates a current output in one of two ways: 1) the sum of a fundamental frequency
current, and pure harmonic, or 2) the sum of a fundamental frequency current and a DC rectified signal of
the fundamental.
Figure 1 shows the sum of a fundamental frequency current of 60Hz with a 50% Harmonic. Figure 2 shows
the sum of a fundamental at 2.25A and the rectified DC current at 1.00A. Figure 3 shows the pure DC
rectified signal without any fundamental current.
OP
R1
R2
I1-I2
I1
I2
DIFFERENTIAL
RELAY
Press [CURRENT] to toggle between I1 and I2
adjustment/display.
Press [PHASE] to display
and adjust phase between
I1 and I2.
Select I1&I2
current mode
NOTE:
Vc is disabled
in this current
mode.
I1
I2
I1-I2
Содержание MTS-1700 SERIES
Страница 30: ...TABLE OF CONTENTS xxx MTS 1700 SERIES OPERATION AND REFERENCE MANUAL MANTA TEST SYSTEMS CU A002 15A ...
Страница 38: ...INTRODUCTION Section 1 1 8 MTS 1700SERIESOPERATIONANDREFERENCEMANUAL MANTA TEST SYSTEMS CU A002 15A ...
Страница 44: ...SPECIFICATIONS Section 2 2 6 MTS 1700 SERIES OPERATION AND REFERENCE MANUAL MANTA TEST SYSTEMS CU A002 15A ...
Страница 248: ...FAULT PLAYBACK Section 7 7 12 MTS 1700 SERIES OPERATION AND REFERENCE MANUAL MANTA TEST SYSTEMS CU A002 15A ...
Страница 262: ...SERVICING Section 8 8 14 MTS 1700 SERIES OPERATION ANDREFERENCE MANUAL MANTA TEST SYSTEMS CU A002 15A ...
Страница 320: ...PROGRAMMABLE DIGITAL I O CHANNELS A 14 MTS 1700 SERIES OPERATION AND REFERENCE MANUAL MANTA TEST SYSTEMS CU A002 15A ...
Страница 340: ...E 4 MTS 1700 SERIES OPERATION AND REFERENCE MANUAL MANTA TEST SYSTEMS CU A002 15A ...
Страница 344: ...GLOSSARY F 4 MTS 1700 SERIES OPERATION AND REFERENCE MANUAL MANTA TEST SYSTEMS CU A002 15A ...