MTS-1750 HIGH CURRENT SOURCE - Section 10
10-10 MTS-1700 SERIES OPERATION AND REFERENCE MANUAL
MANTA TEST SYSTEMS
CU A002 15A
10.4.2.3.2 Current Adjustment and Display
Current is selected and adjusted, just as in I3-WYE current mode. The maximum output is 150A per phase.
The measured value on the [VALUE DISPLAY] is the total paralleled current through the load. The
displayed quantity depends on the [FAULT MODE] selection, as shown in the table in Section 9.4.3.
The fault current can be set without applying it to the load by using the fault current preset feature (see
Section 4.6.9).
10.4.2.3.3 RS-232 Programming
The three-phase current output is programmed similar to the I3-WYE current mode using the AIA, AIB,
AIC, IPR, IFI, IFF, IRR, IPO commands (see Sections 6.2.6.1 and 6.2.6.2) with the exception that the
maximum value is 150A.
10.4.3 Alarms
When the output of the MTS-1750 is overloaded, the [ALARM LED] will illuminate. The nature of the
alarm (overtemperature or current/power overload) will be displayed on the MTS-1710 [MODE/MENU
DISPLAY].
10.4.4 Application of Advanced Capabilities
Almost all the advanced capabilities of the MTS-1710 and MTS-1720 are directly applicable to the MTS-
1750. The capabilities have been extended to apply to the three-phase current system in a logical manner.
These include:
• Separate prefault, fault, and postfault settings in all fault modes
• Stepping, ramping and fault duration in all fault modes
• Variable frequency and harmonic outputs
• Individual phase angle and amplitude adjustment
• Phase sequence: positive and negative
• Dynamic measurement mode: auto, RMS, peak
• Auto-reclose time delay
• Reclose-into-fault events
• Breaker time
• Trip type (3-pole/ 1-pole)
• Fault incidence angle
• Complete RS-232 programmability
• Programmable waveform
• Fault playback
• Current paralleling
• Multi-system synchronization
10.4.4.1 INDIVIDUAL PHASE AND AMPLITUDE ADJUSTMENT WITH THE MTS-1750.
For the MTS-1710 + MTS-1750 configuration, the current amplitude is programmed by the AI1#,#
command (150A maximum), and the current phase angle is programmed by the PHS#,#,4 command.
Содержание MTS-1700 SERIES
Страница 30: ...TABLE OF CONTENTS xxx MTS 1700 SERIES OPERATION AND REFERENCE MANUAL MANTA TEST SYSTEMS CU A002 15A ...
Страница 38: ...INTRODUCTION Section 1 1 8 MTS 1700SERIESOPERATIONANDREFERENCEMANUAL MANTA TEST SYSTEMS CU A002 15A ...
Страница 44: ...SPECIFICATIONS Section 2 2 6 MTS 1700 SERIES OPERATION AND REFERENCE MANUAL MANTA TEST SYSTEMS CU A002 15A ...
Страница 248: ...FAULT PLAYBACK Section 7 7 12 MTS 1700 SERIES OPERATION AND REFERENCE MANUAL MANTA TEST SYSTEMS CU A002 15A ...
Страница 262: ...SERVICING Section 8 8 14 MTS 1700 SERIES OPERATION ANDREFERENCE MANUAL MANTA TEST SYSTEMS CU A002 15A ...
Страница 320: ...PROGRAMMABLE DIGITAL I O CHANNELS A 14 MTS 1700 SERIES OPERATION AND REFERENCE MANUAL MANTA TEST SYSTEMS CU A002 15A ...
Страница 340: ...E 4 MTS 1700 SERIES OPERATION AND REFERENCE MANUAL MANTA TEST SYSTEMS CU A002 15A ...
Страница 344: ...GLOSSARY F 4 MTS 1700 SERIES OPERATION AND REFERENCE MANUAL MANTA TEST SYSTEMS CU A002 15A ...