A.6.5.2 EXAMPLES.
Example 1 Simple Pulse Output.
The following command sequence sets channel 1 output to 0 in prefault state, and produces a 50ms wide
positive pulse after 100ms in the fault state, as illustrated in Figure A-1(a).
DIO,OCL
<- clear output settings
DYN
DIO,OUT0,0,%10
<- channel 1 prefault level=0
DIO,ODY100,%10,%10
<- set channel 1 to 1 100ms after FAULT
DIO,ODY150,0,%10
<- set channel 1 to 0 150ms after FAULT
STR
<- initiate fault using STR command (or use external trigger)
Example 2 Simulated Permissive Trip Signal.
The following command sequence sets channel 2 output to 0 in prefault state, to 1 60 ms after the start of
FAULT state, and back to 0 in postfault, simulating a permissive trip signal, as illustrated in Figure A-1(b).
DIO,OCL
<- clear output settings
DYN
DIO,OUT0,0,%100
<- channel 2 prefault level=0
DIO,ODY60,%100,%100
<- set channel 2 to 1 60ms after FAULT
DIO,OUT2,0,%100
<- set channel 2 to 0 in postfault
STR
<- initiate fault using STR command (or use external trigger)
FIGURE A-1. DIGITAL OUTPUT EXAMPLES
POSTFAULT
FAULT
PREFAULT
(a) Example 1
(b) Example 2
(c) Example 3
Channel
1
0 ms
100 ms
150 ms
60 ms
0 ms
2
Channel
Channel
0
1
2
3
ms
0
25 40
106
Содержание MTS-1700 SERIES
Страница 30: ...TABLE OF CONTENTS xxx MTS 1700 SERIES OPERATION AND REFERENCE MANUAL MANTA TEST SYSTEMS CU A002 15A ...
Страница 38: ...INTRODUCTION Section 1 1 8 MTS 1700SERIESOPERATIONANDREFERENCEMANUAL MANTA TEST SYSTEMS CU A002 15A ...
Страница 44: ...SPECIFICATIONS Section 2 2 6 MTS 1700 SERIES OPERATION AND REFERENCE MANUAL MANTA TEST SYSTEMS CU A002 15A ...
Страница 248: ...FAULT PLAYBACK Section 7 7 12 MTS 1700 SERIES OPERATION AND REFERENCE MANUAL MANTA TEST SYSTEMS CU A002 15A ...
Страница 262: ...SERVICING Section 8 8 14 MTS 1700 SERIES OPERATION ANDREFERENCE MANUAL MANTA TEST SYSTEMS CU A002 15A ...
Страница 320: ...PROGRAMMABLE DIGITAL I O CHANNELS A 14 MTS 1700 SERIES OPERATION AND REFERENCE MANUAL MANTA TEST SYSTEMS CU A002 15A ...
Страница 340: ...E 4 MTS 1700 SERIES OPERATION AND REFERENCE MANUAL MANTA TEST SYSTEMS CU A002 15A ...
Страница 344: ...GLOSSARY F 4 MTS 1700 SERIES OPERATION AND REFERENCE MANUAL MANTA TEST SYSTEMS CU A002 15A ...