ADVANCED OPERATION - Section 5
MTS-1700 SERIES OPERATION AND REFERENCE MANUAL 5-25
CU A002 15A
MANTA TEST SYSTEMS
5.10.3.4 I1 & I2 CT TAPS FOR CURRENT RATIO DISPLAYS.
The I1 and I2 CT taps can be programmed into the menu for use in the current ratio and percent slope display
calculations. These are accessed under the DISP RATIOS CURRENT-RATIOS I1-CT and DISP RATIOS
CURRENT-RATIOS I2-CT selections.
The default value is 1.0 A, and the programmable range is 0.1A to 20.0A.
5.10.3.5 VOLTS-PER-HERTZ RATIO DISPLAY.
This display mode shows the present voltage divided by the present frequency. This is useful when testing
volts-per-Hertz relays.
5.10.4 Power Display Modes
These display modes allow direct display of the single-phase power quantities: kWatts, kVars, kVA, and
Power Factor.
These modes are useful for checking devices, such as Watt and Var transducers, and reverse power relays.
The power readings are available under the DISP POWER selection in the menu.
The power quantities are computed from the presently selected voltage, current and phase angle readings
(which may be
Φ
-N or
Φ
-
Φ
quantities). Because of special phase angle measurements made in I1&I2
current mode, the kWATT, kVAR and Power Factor readings are unavailable in this current mode. Any
invalid or overflow values are indicated by “-----” on the display.
5.11 ADVANCED POSTFAULT FEATURES
This section describes advanced features of the MTS-1710’s postfault state.
5.11.1 Breaker Time
This simulates the breaker operating time while specifing the length of time the fault quantities are
maintained following the relay trip.
Normally, this is set to zero. It may be set to a specific value when testing devices which require true
simulation of breaker operation to perform such functions as fault recording or fault location. The breaker
time may be set via the menu under SETTINGS POSTFAULT BRKR-TIME.
While the breaker time is shown on the [MODE/MENU DISPLAY], pressing the [TIME] button toggles
between display in seconds and cycles.
5.11.2 Auto-Reclose Simulation
5.11.2.3 AUTO-RECLOSE TIME DELAY.
BREAKER-TIME:
0.034 SEC
Содержание MTS-1700 SERIES
Страница 30: ...TABLE OF CONTENTS xxx MTS 1700 SERIES OPERATION AND REFERENCE MANUAL MANTA TEST SYSTEMS CU A002 15A ...
Страница 38: ...INTRODUCTION Section 1 1 8 MTS 1700SERIESOPERATIONANDREFERENCEMANUAL MANTA TEST SYSTEMS CU A002 15A ...
Страница 44: ...SPECIFICATIONS Section 2 2 6 MTS 1700 SERIES OPERATION AND REFERENCE MANUAL MANTA TEST SYSTEMS CU A002 15A ...
Страница 248: ...FAULT PLAYBACK Section 7 7 12 MTS 1700 SERIES OPERATION AND REFERENCE MANUAL MANTA TEST SYSTEMS CU A002 15A ...
Страница 262: ...SERVICING Section 8 8 14 MTS 1700 SERIES OPERATION ANDREFERENCE MANUAL MANTA TEST SYSTEMS CU A002 15A ...
Страница 320: ...PROGRAMMABLE DIGITAL I O CHANNELS A 14 MTS 1700 SERIES OPERATION AND REFERENCE MANUAL MANTA TEST SYSTEMS CU A002 15A ...
Страница 340: ...E 4 MTS 1700 SERIES OPERATION AND REFERENCE MANUAL MANTA TEST SYSTEMS CU A002 15A ...
Страница 344: ...GLOSSARY F 4 MTS 1700 SERIES OPERATION AND REFERENCE MANUAL MANTA TEST SYSTEMS CU A002 15A ...