RS-232C INTERFACE - Section 6
MTS-1700 SERIES OPERATION AND REFERENCE MANUAL 6-9
CU A002 15A
MANTA TEST SYSTEMS
6.2.6 Current Control
6.2.6.1 CURRENT CONTROL COMMANDS.
Command Description
IMD#
Current Mode
•
Set the Current Mode.
•
Valid values are 0-9.
0
- I2-HARMONIC
1 - I4(DC)
2 - I1-HIGH
3 - I1-LOW
4 - I1&I2
5 - I3 (If the MTS-1720 is available, I3-WYE will be selected)
6 - I1-HIGH-AUX
7 - I1-LOW-AUX
8 - I3-AUX
9 - I3-PARALLEL
AI1#
Amplitude I1
•
Sets the I1 prefault current value.
•
In I1-LOW current mode, valid values are 0 - 30.00 (amps).
•
In I1-LOW current mode with one MTS-1750 connected, valid values are 0 -
150.0 (amps).
•
In I1-HIGH current mode, valid values are 0 - 90.0 (amps).
•
In I1&I2 current mode, valid values are 0 - 65.0 (amps) for I1.
•
In I3 current mode, this command sets the I3 prefault level. Valid values are 0 -
30.00 (amps).
•
Note that prefault must be turned on (using the PRF1 command) for this value to
be applied to the outputs in prefault state.
•
In I3-PARALLEL current mode, this command sets the prefault current from the
MTS-1710+MTS-1720 (and optional three MTS-1750s) paralleled output.
•
With the MTS-1710 + MTS-1720 only, valid values are 0 - 90.00 A.
•
With the MTS-1710 + MTS-1720 + three MTS-1750s, valid values are 0 -
450.0 A.
•
All three current channels must be paralleled together to obtain the
programmed value of current.
•
Each current is set to one-third of the programmed value.
IFI#
Initial Fault Current
•
Sets the fault initial current value.
•
In I1-LOW current mode, valid values are 0 - 30.00 (amps).
•
In I1-LOW current mode with one MTS-1750 connected, valid values are 0 -
150.0 (amps).
•
In I1-HIGH current mode, valid values are 0 - 90.0 (amps).
•
In I3 and I3-WYE current modes, this command sets the I3 initial fault level.
Valid values are 0 - 30.00 (amps).
•
This value is only used for I1-LOW, I1-HIGH I3, and I3-WYE current modes.
Содержание MTS-1700 SERIES
Страница 30: ...TABLE OF CONTENTS xxx MTS 1700 SERIES OPERATION AND REFERENCE MANUAL MANTA TEST SYSTEMS CU A002 15A ...
Страница 38: ...INTRODUCTION Section 1 1 8 MTS 1700SERIESOPERATIONANDREFERENCEMANUAL MANTA TEST SYSTEMS CU A002 15A ...
Страница 44: ...SPECIFICATIONS Section 2 2 6 MTS 1700 SERIES OPERATION AND REFERENCE MANUAL MANTA TEST SYSTEMS CU A002 15A ...
Страница 248: ...FAULT PLAYBACK Section 7 7 12 MTS 1700 SERIES OPERATION AND REFERENCE MANUAL MANTA TEST SYSTEMS CU A002 15A ...
Страница 262: ...SERVICING Section 8 8 14 MTS 1700 SERIES OPERATION ANDREFERENCE MANUAL MANTA TEST SYSTEMS CU A002 15A ...
Страница 320: ...PROGRAMMABLE DIGITAL I O CHANNELS A 14 MTS 1700 SERIES OPERATION AND REFERENCE MANUAL MANTA TEST SYSTEMS CU A002 15A ...
Страница 340: ...E 4 MTS 1700 SERIES OPERATION AND REFERENCE MANUAL MANTA TEST SYSTEMS CU A002 15A ...
Страница 344: ...GLOSSARY F 4 MTS 1700 SERIES OPERATION AND REFERENCE MANUAL MANTA TEST SYSTEMS CU A002 15A ...