ADVANCED OPERATION - Section 5
5-4 MTS-1700 SERIES OPERATION AND REFERENCE MANUAL
MANTA TEST SYSTEMS
CU A002 15A
Exiting the menu:
The [MODE/MENU] button may be pressed at any time to exit the menu.
Re-entering the previously or last visited menu screen:
Pressing [PREVIOUS] while in the menu will return you to the previous menu. Pressing the [PREVIOUS]
button when not in the menu will allow you to re-enter the last visited menu screen.
5.1.2 Special Notes
Both the [FAULT] and the [STOP/RESET] button are enabled while the menu is active. This is handy for
doing tests such as response time checks, power swing, or df/dt relay elements in which some menu
accessible parameter must be adjusted between trials.
For example, checking the response time of a relay may require adjusting the “Current duration” setting via
the menu. The test can be performed without exiting the menu by pressing [FAULT], and then [STOP/
RESET] to clear.
The duration can then be immediately changed for the next trial, and the test re-run by pressing [FAULT].
In this manner, trials may be performed successively to find the response time.
A power swing test is similar, except that a current or voltage ramp rate is varied between tests, and a df/dt
relay test is similarly performed by varying the frequency ramp rate between tests.
5.2 RAMPING & FAULT DURATION
Simultaneous and independent ramping of the following four parameters is possible:
Frequency (in variable frequency mode)
Phase angle
Fault voltage
Fault current
Refer to Figure 5.3 to see the basic ramp and duration sequences.
The start trigger causes the four parameters to instantaneously change to the initial fault values. For each
parameter, if ramping is programmed, the parameter will ramp at the programmed rate until the final value
is reached. After this, if a duration is programmed, the final value will be held for the programmed duration,
after which the postfault value is output.
If a duration isn’t programmed, the final value will be held until a stop trigger occurs. Ramping only occurs
in dynamic operation mode. At any point in this sequence, a stop trigger may occur, forcing the output
immediately to the postfault value.
To set ramp (initial, rate, and final) values, the MTS-1710 must be in static operation mode. Only the initial
fault levels can be modified in dynamic mode--if and only if--the ramp rate has been set off.
Содержание MTS-1700 SERIES
Страница 30: ...TABLE OF CONTENTS xxx MTS 1700 SERIES OPERATION AND REFERENCE MANUAL MANTA TEST SYSTEMS CU A002 15A ...
Страница 38: ...INTRODUCTION Section 1 1 8 MTS 1700SERIESOPERATIONANDREFERENCEMANUAL MANTA TEST SYSTEMS CU A002 15A ...
Страница 44: ...SPECIFICATIONS Section 2 2 6 MTS 1700 SERIES OPERATION AND REFERENCE MANUAL MANTA TEST SYSTEMS CU A002 15A ...
Страница 248: ...FAULT PLAYBACK Section 7 7 12 MTS 1700 SERIES OPERATION AND REFERENCE MANUAL MANTA TEST SYSTEMS CU A002 15A ...
Страница 262: ...SERVICING Section 8 8 14 MTS 1700 SERIES OPERATION ANDREFERENCE MANUAL MANTA TEST SYSTEMS CU A002 15A ...
Страница 320: ...PROGRAMMABLE DIGITAL I O CHANNELS A 14 MTS 1700 SERIES OPERATION AND REFERENCE MANUAL MANTA TEST SYSTEMS CU A002 15A ...
Страница 340: ...E 4 MTS 1700 SERIES OPERATION AND REFERENCE MANUAL MANTA TEST SYSTEMS CU A002 15A ...
Страница 344: ...GLOSSARY F 4 MTS 1700 SERIES OPERATION AND REFERENCE MANUAL MANTA TEST SYSTEMS CU A002 15A ...