MTS-1720 TWO CHANNEL CURRENT SOURCE - Section 9
9-14 MTS-1700 SERIES OPERATION AND REFERENCE MANUAL
MANTA TEST SYSTEMS
CU A002 15A
FIGURE 9.9 THREE-PHASE (
Φ
-
Φ
) FAULT
Example To simulate the above three-phase-to-ground fault, set up the following values:
Fault mode
Fault state
Current
Voltage
Phase V-I
3
Φ
A-B
Prefault
1.73A
120V
10.0
°
3
Φ
A-B
Fault
10.4A
34.6V
70.0
°
3
Φ
A-B
Postfault
1.73A
120V
10.0
°
FIGURE 9.10 THREE-PHASE (
Φ
-N) FAULT
Figure 9.10 is the same as Figure 9.9, except that 3
Φ
(
Φ
-N) fault type has been selected. In this way, phase-
to-neutral currents and voltages are measured.
9.4.2.4 2
Φ
-N FAULT TYPE.
The 2
Φ
-N fault type simulates 2
Φ
-ground faults.
When this fault type is selected, the current display shows the phase current (Iab, Ibc or Ica), as selected by
the fault phase. This is
times the line current (Ia, Ib or Ic).
In this fault type, the currents in the two selected fault phases are adjusted to the same amplitude
simultaneously. The unfaulted phase always will remain at its nominal
Φ
-N current setting and prefault
angle.
In the prefault state, the interphase angles on the voltages and currents are set to 120
°
.
70 deg.
20V
6.0A
10 deg.
70V
1.0A
PHASE V-I:
VOLTAGE:
CURRENT:
PREFAULT FAULT
TYPICAL SETTINGS
0
FAULT
PREFAULT
Va
Vc
Vb
Ib
Ic
Ic
Ib
Ia
Vb
Vc
Va
Ia
FAULT MODE = 30 A-N
3
Iab
Ica
Ibc
Vbc
Vca
Vab
FAULT
0
TYPICAL SETTINGS
PREFAULT FAULT
CURRENT:
VOLTAGE:
PHASE V-I:
1.73A
120V
10 deg.
10.4A
34.6V
70 deg.
Vab
Vca
Vbc
Ica
Iab
Ibc
PREFAULT
FAULT MODE = 30 A-B
Содержание MTS-1700 SERIES
Страница 30: ...TABLE OF CONTENTS xxx MTS 1700 SERIES OPERATION AND REFERENCE MANUAL MANTA TEST SYSTEMS CU A002 15A ...
Страница 38: ...INTRODUCTION Section 1 1 8 MTS 1700SERIESOPERATIONANDREFERENCEMANUAL MANTA TEST SYSTEMS CU A002 15A ...
Страница 44: ...SPECIFICATIONS Section 2 2 6 MTS 1700 SERIES OPERATION AND REFERENCE MANUAL MANTA TEST SYSTEMS CU A002 15A ...
Страница 248: ...FAULT PLAYBACK Section 7 7 12 MTS 1700 SERIES OPERATION AND REFERENCE MANUAL MANTA TEST SYSTEMS CU A002 15A ...
Страница 262: ...SERVICING Section 8 8 14 MTS 1700 SERIES OPERATION ANDREFERENCE MANUAL MANTA TEST SYSTEMS CU A002 15A ...
Страница 320: ...PROGRAMMABLE DIGITAL I O CHANNELS A 14 MTS 1700 SERIES OPERATION AND REFERENCE MANUAL MANTA TEST SYSTEMS CU A002 15A ...
Страница 340: ...E 4 MTS 1700 SERIES OPERATION AND REFERENCE MANUAL MANTA TEST SYSTEMS CU A002 15A ...
Страница 344: ...GLOSSARY F 4 MTS 1700 SERIES OPERATION AND REFERENCE MANUAL MANTA TEST SYSTEMS CU A002 15A ...