ADVANCED OPERATION - Section 5
5-30 MTS-1700 SERIES OPERATION AND REFERENCE MANUAL
MANTA TEST SYSTEMS
CU A002 15A
FIGURE 5.12 POSTFAULT SEQUENCE EXAMPLE 2
5.12 PHASE ADJUSTMENT MODE
This setting determines the manner in which phase angles are changed by the user.
The phase adjustment mode is selected via the menu under SETTINGS MODES PHASE INDIVIDUAL-
ADJ-MODE ENABLE. This menu appears as follows:
5.12.1 Normal Phase Adjustment Mode
The default setting is “Normal” where phase adjustment automatically adjusts the appropriate current(s)
and/or voltage(s). This is dependent upon the current mode.
Ib
Vb
Prefault
Fault
Reclose
MTS-1710
STATE
Prefault
Fault
Postfault
Va
Vc
Ia
Ic
Auto-reclose
time delay
Breaker
operate
time
Relay
Trip
INDIV-VOLT INDIV-CUR
PHS-ADJ MODE: NORMAL
Содержание MTS-1700 SERIES
Страница 30: ...TABLE OF CONTENTS xxx MTS 1700 SERIES OPERATION AND REFERENCE MANUAL MANTA TEST SYSTEMS CU A002 15A ...
Страница 38: ...INTRODUCTION Section 1 1 8 MTS 1700SERIESOPERATIONANDREFERENCEMANUAL MANTA TEST SYSTEMS CU A002 15A ...
Страница 44: ...SPECIFICATIONS Section 2 2 6 MTS 1700 SERIES OPERATION AND REFERENCE MANUAL MANTA TEST SYSTEMS CU A002 15A ...
Страница 248: ...FAULT PLAYBACK Section 7 7 12 MTS 1700 SERIES OPERATION AND REFERENCE MANUAL MANTA TEST SYSTEMS CU A002 15A ...
Страница 262: ...SERVICING Section 8 8 14 MTS 1700 SERIES OPERATION ANDREFERENCE MANUAL MANTA TEST SYSTEMS CU A002 15A ...
Страница 320: ...PROGRAMMABLE DIGITAL I O CHANNELS A 14 MTS 1700 SERIES OPERATION AND REFERENCE MANUAL MANTA TEST SYSTEMS CU A002 15A ...
Страница 340: ...E 4 MTS 1700 SERIES OPERATION AND REFERENCE MANUAL MANTA TEST SYSTEMS CU A002 15A ...
Страница 344: ...GLOSSARY F 4 MTS 1700 SERIES OPERATION AND REFERENCE MANUAL MANTA TEST SYSTEMS CU A002 15A ...