![Manta MTS-1700 SERIES Скачать руководство пользователя страница 245](http://html1.mh-extra.com/html/manta/mts-1700-series/mts-1700-series_operation-and-reference-manual_1723616245.webp)
FAULT PLAYBACK - Section 7
MTS-1700 SERIES OPERATION AND REFERENCE MANUAL 7-9
CU A002 15A
MANTA TEST SYSTEMS
7.5 REQUIRED SETTINGS FOR FAULT PLAYBACK
7.5.1 MTS-1710 Only
The following settings are required to set up the MTS-1710 to perform fault playback (8-bit):
RS-232 Command
Setting
REM
Remote control mode
DYN
Dynamic Operation mode
IMD#
Select I1-LOW or I3 current mode only
FMD0
Φ
-N fault type (FMD1 and FMD2 also may be used here)
LIN
Line frequency mode
AVA#
Set maximum RMS amplitudes using AVA, AVB, AVC, AIA commands
AVB#
(Note that prefault outputs will be forced to zero)
AVC#
AIA#
POF#
Select desired postfault output
RCM#
Select fault playback mode. After fault playback mode is selected, the “FLT-REC”
annunciator will appear in the upper right corner of the [MODE/MENU
DISPLAY]
RCR#
Set playback rate
RCD#,#,#,#
Download fault data (Va, Vb, Vc, I)
RCD#,#,#,#
<- repeat for up to 60,000 samples
7.5.2 MTS-1710+MTS-1720
The following settings are required to set up the MTS-1710 & MTS-1720 to perform full 3
Φ
-voltage/3
Φ
-
current fault playback in I3-WYE current mode (8-bit):
RS-232 Command
Setting
REM
Remote control mode
DYN
Dynamic Operation mode
IMD5
Select I3-WYE current mode
FMD0
Φ
-N fault type (FMD1 and FMD2 also may be used here)
LIN
Line frequency mode
AVA#
Set maximum RMS amplitudes using AVA, AVB, AVC, AIA, AIB, AIC
commands
AVB#
(Note that prefault outputs will be forced to zero)
AVC#
AIA#
AIB#
AIC#
POF#
Select desired postfault output
RCM#
Select fault playback mode. After fault playback mode is selected, the “FLT-REC”
annunciator will appear in the upper right
corner
of
the
[MODE/MENU
DISPLAY]
RCR#
Set playback rate
RCD#,#,#,#,#,#
Download fault data (Va, Vb, Vc, Ia, Ib, Ic)
RCD#,#,#,#,#,#
<- repeat for up to 60,000 samples
Содержание MTS-1700 SERIES
Страница 30: ...TABLE OF CONTENTS xxx MTS 1700 SERIES OPERATION AND REFERENCE MANUAL MANTA TEST SYSTEMS CU A002 15A ...
Страница 38: ...INTRODUCTION Section 1 1 8 MTS 1700SERIESOPERATIONANDREFERENCEMANUAL MANTA TEST SYSTEMS CU A002 15A ...
Страница 44: ...SPECIFICATIONS Section 2 2 6 MTS 1700 SERIES OPERATION AND REFERENCE MANUAL MANTA TEST SYSTEMS CU A002 15A ...
Страница 248: ...FAULT PLAYBACK Section 7 7 12 MTS 1700 SERIES OPERATION AND REFERENCE MANUAL MANTA TEST SYSTEMS CU A002 15A ...
Страница 262: ...SERVICING Section 8 8 14 MTS 1700 SERIES OPERATION ANDREFERENCE MANUAL MANTA TEST SYSTEMS CU A002 15A ...