3 Wiring
3.1 Wiring Practices
•
Recommended wire is to be rated for minimum 75°C, 600 VAC, vinyl sheathed.
•
Ensure that the encoder wiring is less than 300 feet unless fiber optic cables are used.
•
Ensure that the encoder wiring is isolated from the power wiring.
•
Ensure that the encoder wiring shield is grounded only at the VFD end.
•
Connect the incoming three-phase AC source to terminals R/L1, S/L2, T/L3.
•
Connect the Motor leads to terminals U/T1, V/T2, W/T3.
•
Install a line reactor between the output of the VFD in applications that require a disconnecting means between
the VFD’s output and motor. Use a “make before break” auxiliary contact with the disconnect means and the
hardware base block of the VFD.
•
Use hard contacts between the PLC output and the VFD 120/24/48 VAC interface board. If using a solid state
output from a PLC (TRIAC) to a 120/24/48 VAC input card, use a 5K
, 5W resistor between the signal and X2.
•
If the power source is 500 kVA or greater, or more than 10 times the VFD kVA rating, ensure there is at least
3% impedance between the power source and the VFD input. To accomplish this, a DC reactor can be installed
between VFD ter1 and +2, or an AC line reactor can be used on the input of the VFD. Excessive peak
currents could damage the input power supply circuit if there is not enough impedance.
•
Comply with the Suggested Circuit Protection and Wire Size specifications in
.
•
Use time delay fuses, which are sized at 150% of VFD’s continuous rated input current, for wiring protection.
•
Use appropriate R-C or MOV type surge absorbers across the coil of all contactors and relays in the system.
Failure to do so could result in noise-related, nuisance fault incidents.
•
Use external dynamic braking resistors for all applications.
•
Do not ground the VFD with any large-current machines.
•
Before using any welding or high-current machines near the crane, disconnect all line and ground wiring.
•
Do not let the wiring leads come in contact with the VFD enclosure.
•
Do not connect power factor correction capacitors to the VFD input or output; use a sine wave filter.
•
The VFD and motor must be hardwired together. Do not use sliding collector bars.
•
If there is a user input device or interface board that is remote, use shielded cable between the VFD input
terminals and the interface output terminals or user input device(s).
•
Before turning on the VFD, check the output circuit (U/T1, V/T2 and W/T3) for possible short circuits and
ground faults.
•
Increase the wire size by one gauge for every 250 feet (76.2 meters) between the VFD and motor; suggested
for center driven cranes, trolleys, and bridges (voltage drop is significant at low frequencies).
WARNING
Before you wire the VFD, review the following practices to help ensure that your system is wired properly.
Содержание Impulse G+ series 4
Страница 20: ...IMPULSE G VG Series 4 Technical Manual November 2022 Page 20 Figure 2 1 Capacitor Reform Diagrams...
Страница 30: ...IMPULSE G VG Series 4 Technical Manual November 2022 Page 30 Figure 3 1 Typical Connection Diagram...
Страница 53: ...IMPULSE G VG Series 4 Technical Manual November 2022 Page 53 4 3 2 Menu Structure Figure 4 1 Menu Structure...
Страница 243: ...IMPULSE G VG Series 4 Technical Manual November 2022 Page 243 Figure B 5 Figure B 6 Figure B 7...
Страница 246: ...IMPULSE G VG Series 4 Technical Manual November 2022 Page 246 Figure B 8 Figure B 9 Figure B 10 Figure B 11...
Страница 248: ...IMPULSE G VG Series 4 Adjustable Frequency Vector Crane Controls Technical Manual November 2022...