5.4 Motor Parameters
•
E01 V/f Pattern
•
E02 Motor Setup
•
E03 Test Mode Configuration
5.4.1 Voltage/Frequency (V/f) Pattern
Table 5-55: V/f Pattern Parameter Settings
Figure 5-24: Output Voltage
An OPE10 error will occur if the following conditions are not met:
E01-05
≥
E01-12
≥
E01-13
≥
E01-08
≥
E01-10
E01-04
≥
E01-11
≥
E01-06
≥
E01-07
≥
E01-09
NOTE:
In Flux Vector, E01-03 is hidden, and the V/f pattern values will be adjusted by the Auto-Tuning function.
Parameter
Display
Function
Range
Default
E01-01
Input Voltage
VFD input voltage used as the max and base
voltage by preset V/f patterns (E01-03 = 0 to
E). It also adjusts the levels of protective
features (e.g., Overvoltage, braking transistor
turn-on, stall prevention, etc).
230V: 155–255 VAC
460V: 310–510 VAC
575V: 446–733 VAC
230
460
575
WARNING
VFD input voltage (not motor voltage) must be set in E01-01 for the protective features of the VFD to function
properly. Failure to do so may result in equipment damage and/or death or personal injury.
Содержание Impulse G+ series 4
Страница 20: ...IMPULSE G VG Series 4 Technical Manual November 2022 Page 20 Figure 2 1 Capacitor Reform Diagrams...
Страница 30: ...IMPULSE G VG Series 4 Technical Manual November 2022 Page 30 Figure 3 1 Typical Connection Diagram...
Страница 53: ...IMPULSE G VG Series 4 Technical Manual November 2022 Page 53 4 3 2 Menu Structure Figure 4 1 Menu Structure...
Страница 243: ...IMPULSE G VG Series 4 Technical Manual November 2022 Page 243 Figure B 5 Figure B 6 Figure B 7...
Страница 246: ...IMPULSE G VG Series 4 Technical Manual November 2022 Page 246 Figure B 8 Figure B 9 Figure B 10 Figure B 11...
Страница 248: ...IMPULSE G VG Series 4 Adjustable Frequency Vector Crane Controls Technical Manual November 2022...