5.1.4 Stop Method
Selects the stopping method suitable for the application.
Table 5-5: Stop Method Parameter Settings
* Initial value is determined by X-Press Programming (
or
5.1.4.1
Decel to Stop (B03-03 = 0)
Upon removal of the FWD or REV run command, the motor decelerates at a rate determined by the time set in
deceleration time 1 (B05-02) and DC injection braking is applied after the DC injection start frequency D01-01 has
been reached. If the deceleration time is set too short or the load inertia is too large, an overvoltage fault (OV) or
deviation (DEV) may occur during deceleration. In this case, increase the deceleration time or verify the braking
resistor is sized correctly.
Figure 5-2: Decel to Stop
Parameter
Display
Function
Range
Default
B03-03
Stopping Method
Determines stop method.
0, 1, 4, 6
G+: 0*
VG+: 6*
0 Decel to Stop
(
)
1 Coast to Stop
(
)
4 Decel with timer
(Traverse only)
(
)
6 No Load Brake
See No-Load Brake Parameter Group
C08 (VG+ only).
Содержание Impulse G+ series 4
Страница 20: ...IMPULSE G VG Series 4 Technical Manual November 2022 Page 20 Figure 2 1 Capacitor Reform Diagrams...
Страница 30: ...IMPULSE G VG Series 4 Technical Manual November 2022 Page 30 Figure 3 1 Typical Connection Diagram...
Страница 53: ...IMPULSE G VG Series 4 Technical Manual November 2022 Page 53 4 3 2 Menu Structure Figure 4 1 Menu Structure...
Страница 243: ...IMPULSE G VG Series 4 Technical Manual November 2022 Page 243 Figure B 5 Figure B 6 Figure B 7...
Страница 246: ...IMPULSE G VG Series 4 Technical Manual November 2022 Page 246 Figure B 8 Figure B 9 Figure B 10 Figure B 11...
Страница 248: ...IMPULSE G VG Series 4 Adjustable Frequency Vector Crane Controls Technical Manual November 2022...