IMPULSE•G+/VG+ Series 4 Technical Manual
November 2022
Page 115
5.3.2 Motor Slip Compensation
As the load becomes larger, the motor speed is reduced and the motor slip increases. The slip compensation
function keeps the motor speed constant under varying load conditions. D02-01 sets the slip compensation gain.
When the gain is “1.0”, the output frequency is increased by 1% of the E01-06 setting at rated current. A setting of
“0.0” results in no slip compensation.
Table 5-45: Motor Slip Compensation Parameter Settings
* Available only for 4810 and 41090 VG+ models.
5.3.3 Torque Compensation
The motor torque requirement changes according to load conditions. Full-range automatic torque boost adjusts the
voltage of the V/f pattern according to the required torque. The VFD automatically adjusts the voltage during
constant-speed operation as well as during acceleration.
The required torque is calculated by the VFD. This ensures smooth operation and power savings.
Output voltage
α
Torque compensation gain x Required torque
When more torque is needed, increase the torque compensation gain in one-tenth (0.1) increments. Increase the
setting when the wiring distance between the VFD and the motor is 100 feet (30.5 meters) or longer. If the motor
generates excessive vibration or oscillates, decrease the torque compensation.
Increasing torque compensation gain increases motor torque, but an excessive increase may cause the following:
•
VFD faults due to motor overexcitation, and/or
•
Motor overheat or excessive vibration.
Increase the torque compensation time constant in 10 ms increments when the motor’s output current is unstable.
Decrease this value when speed response is slow.
Parameter
Display
Function
Range
Default
D02-01
Slip Comp Gain
Slip compensation multiplier.
0.0–2.5
V/f: 0.0
OLV: 1.0
FLV: 1.0
D02-02
Slip Comp Time
Adjusts the slip compensation function delay time
(G+ only).
0–10000 ms
V/f: 2000
OLV: 200
D02-03
Slip Comp Limit
Upper limit for the slip compensation as a
percentage of motor rated slip E02-02 (G+ only).
0–250%
200
D02-04
Slip Comp Regen
Disabled slip compensation during regeneration
(G+ only).
0–2
0
0 Disabled
1 Enabled >6 Hz
2 Enabled >2 Hz
D02-05
Output V Lim Sel
Automatically reduces motor flux when the output
voltage saturates.
0, 1
0
0 Disabled
1 Enabled
D02-13*
Output V Lim Sta
Output Voltage Limit Operation Start Level
70.0–90.0%
85.0
D02-14*
Output V Lim Max
Maximum Output Voltage Limit Level
85.0–100.0%
90.0
D02-15*
Output V Lim Lev
Output Voltage Limit Level
30.0–100.0%
90.0
Содержание Impulse G+ series 4
Страница 20: ...IMPULSE G VG Series 4 Technical Manual November 2022 Page 20 Figure 2 1 Capacitor Reform Diagrams...
Страница 30: ...IMPULSE G VG Series 4 Technical Manual November 2022 Page 30 Figure 3 1 Typical Connection Diagram...
Страница 53: ...IMPULSE G VG Series 4 Technical Manual November 2022 Page 53 4 3 2 Menu Structure Figure 4 1 Menu Structure...
Страница 243: ...IMPULSE G VG Series 4 Technical Manual November 2022 Page 243 Figure B 5 Figure B 6 Figure B 7...
Страница 246: ...IMPULSE G VG Series 4 Technical Manual November 2022 Page 246 Figure B 8 Figure B 9 Figure B 10 Figure B 11...
Страница 248: ...IMPULSE G VG Series 4 Adjustable Frequency Vector Crane Controls Technical Manual November 2022...