IMPULSE•G+/VG+ Series 4 Technical Manual
November 2022
Page 213
Table 6-6: Fault Codes for Option Cards
Display
Card
Description
Cause
Possible Solution
oFA00
SI-
AI-A3
AO-A3
DI-A3
DO-A3
S4I
S4IO
Option Error (CN5-A).
Option
Card Connection Error at Port
CN5-A.
• The option card
installed into port
CN5-A is incompatible.
• A PG- or SI- option
card is connected to
port CN5-A.
• Confirm that the VFD supports
the option card.
• PG option cards are supported
in ports CN5-B and CN5-C only.
Connect the PG option card to
the correct port.
• SI- option cards are supported
in port CN5-A only. Connect the
SI- option card to the correct
port.
oFA01
SI-
AI-A3
AO-A3
DI-A3
DO-A3
S4I
S4IO
Option Fault (CN5-A).
Option
Card at Port CN5-A is not properly
connected or is faulty.
• Option at port CN5-A
was changed during
run.
• Turn the power off and check
the connectors between the
VFD and the option.
oFB00
AO-A3
DO-A3
S4I
S4IO
Option Error (CN5-B).
Option
Card connection error at VFD port
CN5-B.
• The option card
installed into port
CN5-B is incompatible.
• A communication
option card has been
installed in option port
CN5-B.
• Confirm that the VFD supports
the option card.
• Communication option cards are
only supported in port CN5-A. It
is not possible to install more
than one communication option.
oFB01
AO-A3
DO-A3
S4I
S4IO
Option Fault (CN5-B).
Option
Card at Port CN5-B is not properly
connected or is faulty.
• Option at port CN5-B
was changed during
run.
• Turn the power off and check
the connectors between the
VFD and the option.
oFB02
AO-A3
DO-A3
S4I
S4IO
Option Fault (CN5-B).
Two of the
same option cards are connected
simultaneously.
• Duplicate type of
option card is
connected to ports
CN5-A, CN5-B, and
CN5-C.
• AI-A3/DI-A3/SI-: These option
cards may only be connected to
port CN5-A.
• AO-A3/DO-A3: Both of these
options can't be connected at
the same time.
oFC00
AO-A3
DO-A3
S4I
S4IO
Option Error (CN5-C).
Option
Card Connection Error at Port
CN5-C.
• The option card
installed into port
CN5-C is
incompatible.
• A communication
option card has been
installed in option port
CN5-C.
• Confirm that the VFD supports
the option card.
• Communication option cards
are only supported in port CN5-
A. It is not possible to install
more than one communication
option.
oFC01
AO-A3
DO-A3
S4I
S4IO
Option Fault (CN5-C).
Option
Card at Port CN5-C is not properly
connected or is faulty.
• Option at VFD port
CN5-C was changed
during run.
• Turn off the power and check
the connectors between the
VFD and the option.
oFC02
AO-A3
DO-A3
S4I
S4IO
Option Fault (CN5-C).
Two of the
same option cards are connected
simultaneously.
• Duplicate type of
option card is
connected to ports
CN5-A, CN5-B, and
CN5-C.
• AI-A3/DI-A3/SI-: These option
cards may only be connected to
port CN5-A.
• AO-A3/DO-A3: Both of these
options can't be connected at
the same time.
Содержание Impulse G+ series 4
Страница 20: ...IMPULSE G VG Series 4 Technical Manual November 2022 Page 20 Figure 2 1 Capacitor Reform Diagrams...
Страница 30: ...IMPULSE G VG Series 4 Technical Manual November 2022 Page 30 Figure 3 1 Typical Connection Diagram...
Страница 53: ...IMPULSE G VG Series 4 Technical Manual November 2022 Page 53 4 3 2 Menu Structure Figure 4 1 Menu Structure...
Страница 243: ...IMPULSE G VG Series 4 Technical Manual November 2022 Page 243 Figure B 5 Figure B 6 Figure B 7...
Страница 246: ...IMPULSE G VG Series 4 Technical Manual November 2022 Page 246 Figure B 8 Figure B 9 Figure B 10 Figure B 11...
Страница 248: ...IMPULSE G VG Series 4 Adjustable Frequency Vector Crane Controls Technical Manual November 2022...