5.3.6 Dwell
The Dwell function is used to temporarily hold the output frequency at a set reference for a set time. Enable by
setting H01-xx = 65.
Table 5-51: Dwell Function Parameter Settings
Figure 5-22: Dwell Function
Parameter
Display
Function
Range
Default
D08-01
Dwell Ref @ Start
Dwell frequency reference at start.
0.0–150.0 Hz
0.0
D08-02
Dwell Time @ Start
Time duration for the Dwell function at start.
0.0–10.0 sec
0.0
D08-03
Dwell Ref @ Stop
Dwell frequency reference at stop.
0.0–150.0 Hz
0.0
D08-04
Dwell Time @ Stop
Time duration for the Dwell function at stop.
0.0–10.0 sec
0.0