IMPULSE•G+/VG+ Series 4 Technical Manual
November 2022
Page 144
5.6.1.1
Digital Inputs—External Fault
It is sometimes desirable to have at least one external fault input to the VFD. The table below shows the possible
selections for external faults that can be assigned to a digital input (H01-xx or C09-xx).
Table 5-73: External Fault Selection
(1) N.O. = normally open contact; N.C. = normally closed contact
(2) Uses B05-08 timer
Input Type
Detection Method
External Fault Action
MFDI Setting
N.O.
(1)
N.C.
(1)
Always
During Run
Ramp to
Stop
Coast to
Stop
Fast Stop
(2)
Alarm Only
20
24
28
2C
22
26
2A
2E
21
25
29
2D
23
27
2B
2F