Fast commissioning
Leuze electronic GmbH + Co. KG
BCL 248i
16
3.6
Starting the device
Ä
Connect the +18 … 30 V DC supply voltage (typ24 V DC).
ð
The BCL 248i starts up, the PWR, NET and LINK LEDs indicate the operating state.
Tab. 3.1:
Display of operating state
LED
Color
State
Description
PWR
Green
Flashing
Device ok, initialization
Continuous light
Power On, device OK
Briefly off - on
Good read, reading successful
Green - red
Green off – briefly
red – green on
No Read, reading not successful
Yellow
Continuous light
Service mode
Red
Flashing
Warning
Continuous light
Error, device error
NET
Green
Flashing
Initialization
Continuous light
Network mode ok
Orange
Flashing
Topology error
Red
Flashing
Communication error
Continuous light
Network error
LINK
Green
Continuous light
Ethernet connected (LINK)
Yellow
Flashing
Data communication (ACT)
During the initialization phase (power on), the laser is switched on for approx. 2 seconds. A configuration
code can be read in during this time.
NOTICE
Setting the IP address to the Leuze default address
By reading in the configuration code during the initialization phase, the IP address and the sub-
net mask are set to the Leuze default.
IP address: 192.168.60.101
Subnet mask: 255.255.255.0
192.168.060.101
Operating the bar code reader
After connecting a supply voltage of +18 … 30 V DC to the switching input, a read process is activated. In
the standard setting, all common code types for decoding are released. Only the 2/5 Interleaved code type
is limited to 10 digits of code content.
If a code is moved through the reading field, the code content is decoded and forwarded to the superior
system (PLC/PC) via PROFINET-IO.