Parameter | Name:
C00517 | User menu
Data type: INTEGER_32
Index: 24058
d
= 5DFA
h
When a system is installed, parameters must be changed time and again until the system runs satisfactorily. The
user menu of a device serves to create a selection of frequently used parameters to be able to access and change
these parameters quickly.
Setting range
(min. value | unit | max. value)
0
994
Subcodes
Lenze setting
Info
C00517/1
51
: Display of actual speed value
C00517/2
53
: Display of DC-bus voltage
C00517/3
54
: Display of motor current
C00517/4
61
: Display of heatsink temperature
C00517/5
137
: Display of device state
C00517/6
0
C00517/7
0
C00517/8
11
: Reference speed
C00517/9
39
C00517/10
0
C00517/11
12
: Accel. time - main setpoint
C00517/12
13
C00517/13
15
: V/f base frequency
C00517/14
16
: Vmin boost
C00517/15
22
: Imax in motor mode
C00517/16
120
: Motor overload threshold (I
2
xt)
C00517/17
87
: Rated motor speed
C00517/18
99
: Display of firmware version
C00517/19
0
C00517/20
0
;
Read access
;
Write access
CINH
PLC STOP
No transfer
COM
MOT
Scaling factor: 1
Parameter | Name:
C00565 | Resp. to mains phase failure
Data type: UNSIGNED_8
Index: 24010
d
= 5DCA
h
Response to the failure of mains phases
Selection list
(Lenze setting printed in bold)
0 No Reaction
1 Fault
4 WarningLocked
;
Read access
;
Write access
CINH
PLC STOP
No transfer
COM
MOT
Scaling factor: 1
Parameter | Name:
C00574 | Resp. to brake resist. overtemp.
Data type: UNSIGNED_8
Index: 24001
d
= 5DC1
h
Response to overtemperature of the brake resistor
Selection list
(Lenze setting printed in bold)
0 No Reaction
1 Fault
4 WarningLocked
;
Read access
;
Write access
CINH
PLC STOP
No transfer
COM
MOT
Scaling factor: 1