Firmware 03.00 - DMS EN 5.0 - 07/2009
L
199
8400 BaseLine D | Software Manual
Parameter reference
Parameter list | C00222
C00222
C00223
C00224
C00225
C00226
C00227
Parameter | Name:
C00222 | L_PCTRL_1: Vp
Data type: INTEGER_16
Index: 24353
d
= 5F21
h
From version 03.00.00
FB
: Gain factor Vp for the PID process controller
Setting range
(min. value | unit | max. value)
Lenze setting
0.1
500.0
1.0
;
Read access
;
Write access
CINH
PLC STOP
No transfer
COM
MOT
Scaling factor: 10
Parameter | Name:
C00223 | L_PCTRL_1: Tn
Data type: UNSIGNED_16
Index: 24352
d
= 5F20
h
From version 03.00.00
FB
: Reset time Tr for the PID process controller
Setting range
(min. value | unit | max. value)
Lenze setting
20
ms
6000
400 ms
;
Read access
;
Write access
CINH
PLC STOP
No transfer
COM
MOT
Scaling factor: 1
Parameter | Name:
C00224 | L_PCTRL_1: Kd
Data type: UNSIGNED_16
Index: 24351
d
= 5F1F
h
From version 03.00.00
FB
: Derivative-action coefficient Kd for the PID process controller
Setting range
(min. value | unit | max. value)
Lenze setting
0.0
5.0
0.0
;
Read access
;
Write access
CINH
PLC STOP
No transfer
COM
MOT
Scaling factor: 10
Parameter | Name:
C00225 | L_PCTRL_1: MaxLimit
Data type: INTEGER_16
Index: 24350
d
= 5F1E
h
From version 03.00.00
FB
: Maximum output value of the PID process controller
Setting range
(min. value | unit | max. value)
Lenze setting
-199.9
%
199.9
199.9 %
;
Read access
;
Write access
CINH
PLC STOP
No transfer
COM
MOT
Scaling factor: 100
Parameter | Name:
C00226 | L_PCTRL_1: MinLimit
Data type: INTEGER_16
Index: 24349
d
= 5F1D
h
From version 03.00.00
FB
: Minimum output value of the PID process controller
Setting range
(min. value | unit | max. value)
Lenze setting
-199.9
%
199.9
-199.9 %
;
Read access
;
Write access
CINH
PLC STOP
No transfer
COM
MOT
Scaling factor: 100
Parameter | Name:
C00227 | L_PCTRL_1: acceleration time
Data type: UNSIGNED_32
Index: 24348
d
= 5F1C
h
From version 03.00.00
FB
: Acceleration time for the output value of the PID process controller
Setting range
(min. value | unit | max. value)
Lenze setting
0.0
s
999.9
0.1 s
;
Read access
;
Write access
CINH
PLC STOP
No transfer
COM
MOT
Scaling factor: 1000