8400 BaseLine D | Software Manual
Motor control (MCTRL)
Flying restart function
How to parameterise the flying restart function:
1. Activate flying restart circuit in
through "ON".
• Every time the controller is enabled, a synchronisation to the rotating or
standing drive is carried out.
When the Lenze setting is used, most applications do not require additional
controller settings.
If additional settings are necessary, proceed as follows:
2. Define the search mode for the flying restart circuit in
:
• we recommend Lenze default setting "5": Last output frequency
We recommend to set a flying restart current of 10 % ... 25 % of the rated motor
current.
• During a flying restart process, a current is injected into the motor to identify
the speed.
• Reducing the current causes a reduction of the motor torque during the flying
restart process. A short-time starting action or reversing of the motor is
prevented with low flying restart currents.
• An increase of the current improves the robustness of the flying restart
function.