Firmware 03.00 - DMS EN 5.0 - 07/2009
L
187
8400 BaseLine D | Software Manual
Parameter reference
Parameter list | C00097
C00097
C00098
C00099
C00100
C00105
Parameter | Name:
C00097 | Rated motor torque
Data type: UNSIGNED_32
Index: 24478
d
= 5F9E
h
Display of the rated motor torque
• The value displayed here is calculated from different parameters, e.g. the maximum current set in
Display range
(min. value | unit | max. value)
0.00
Nm
99.00
;
Read access
Write access
CINH
PLC STOP
;
No transfer
COM
MOT
Scaling factor: 100
Parameter | Name:
C00098 | Rated device current
Data type: UNSIGNED_16
Index: 24477
d
= 5F9D
h
Display of the rated inverter current which is defined by the integrated power section.
Display range
(min. value | unit | max. value)
0.0
A
999.0
;
Read access
Write access
CINH
PLC STOP
;
No transfer
COM
MOT
Scaling factor: 10
Parameter | Name:
C00099 | Firmware version
Data type: VISIBLE_STRING
Index: 24476
d
= 5F9C
h
Display of the firmware version of the device as string
;
Read access
Write access
CINH
PLC STOP
;
No transfer
COM
MOT
Parameter | Name:
C00100 | Firmware version
Data type: UNSIGNED_8
Index: 24475
d
= 5F9B
h
Display of the firmware version of the device, divided into subsections.
Display range
(min. value | unit | max. value)
0
99
Subcodes
Info
C00100/1
Firmware version - main version
C00100/2
Firmware version - subversion
C00100/3
Firmware version - release
C00100/4
Firmware version build
;
Read access
Write access
CINH
PLC STOP
;
No transfer
COM
MOT
Scaling factor: 1
Parameter | Name:
C00105 | Deceleration time - quick stop
Data type: UNSIGNED_32
Index: 24470
d
= 5F96
h
The set deceleration time determines the ramp slope at quick stop
• If the output frequency falls below the threshold set in
, the DCB DC injection brake is activated.
Note:
The S-ramp time set in
is also effective at quick stop!
In order to reach the required deceleration time for quick stop, set accordingly less time in this parameter.
Setting range
(min. value | unit | max. value)
Lenze setting
0.0
s
999.9
5.0 s
;
Read access
;
Write access
CINH
PLC STOP
No transfer
COM
MOT
Scaling factor: 1000