8400 BaseLine D | Software Manual
Parameter reference
Parameter list | C00024 |
180
L
Firmware 03.00 - DMS EN 5.0 - 07/2009
C00024 |
C00026
C00027
C00028 |
Parameter | Name:
C00024 | Comparison value N_Act
Data type: INTEGER_16
Index: 24551
d
= 5FE7
h
Threshold for the actual speed comparison
• This parameter serves to set a threshold that is compared with the actual speed value.
• When the value falls below this threshold, the
bNactCompare
output of the SB
switches to
TRUE.
• Switching hysteresis = +1 %
Setting range
(min. value | unit | max. value)
Lenze setting
0.0
%
199.9
0.0 %
;
Read access
;
Write access
CINH
PLC STOP
No Transfer
COM
MOT
Scaling factor: 100
Parameter | Name:
C00026 | AINx: Offset
Data type: INTEGER_16
Index: 24549
d
= 5FE5
h
Offset for analog input
Setting range
(min. value | unit | max. value)
-199.9
%
199.9
Subcodes
Lenze setting
Info
C00026/1
0.0 %
AIN1: Offset
;
Read access
;
Write access
CINH
PLC STOP
No Transfer
COM
MOT
Scaling factor: 100
Parameter | Name:
C00027 | AINx: Gain
Data type: INTEGER_32
Index: 24548
d
= 5FE4
h
Gain for analog input
Setting range
(min. value | unit | max. value)
-199.9
%
199.9
Subcodes
Lenze setting
Info
C00027/1
100.0 %
AIN1: Gain
;
Read access
;
Write access
CINH
PLC STOP
No Transfer
COM
MOT
Scaling factor: 100
Parameter | Name:
C00028 | AINx: Input voltage
Data type: INTEGER_16
Index: 24547
d
= 5FE3
h
Display of the input voltage at the analog input
Display range
(min. value | unit | max. value)
-10.0
V
10.0
Subcodes
Info
C00028/1
AIN1: Input voltage
;
Read access
Write access
CINH
PLC STOP
;
No Transfer
COM
MOT
Scaling factor: 100