8400 BaseLine D | Software Manual
Commissioning
Test commissioning
30
L
Firmware 03.00 - DMS EN 5.0 - 07/2009
3.3.2
Test commissioning with terminal control
Commissioning steps
1. Wire the power connections
Make use of the Mounting Instructions supplied with the frequency inverter to carry
out the power connections correctly and in accordance with the requirements of your
device.
2. Wire the control connections
3. If you are sure that the state of the frequency inverter is as delivered from the
manufacturer (Lenze setting), you can skip the following step.
If not, restore the Lenze setting on the frequency inverter:
[3-3]
Setting / resetting the Lenze setting
Wiring of the analog input at X4
Assignment
Terminal control
A1U
Setpoint selection
10 V (= 100 %):
1500 rpm (for 4-pole motor)
Interconnection of the digital inputs at X4
Assignment
Terminal control
DI1 ... DI4: All active = high
RFR
• Controller enable: RFR = high
• Error reset:
High
→
low (edge-controlled)
DI1
DI1: Fixed frequency 1 ... fixed frequency 3,
DI2: Fixed frequency 2 ... fixed frequency 3
see table
DI2
DI3
DCB
DI4
Direction of rotation counter-clockwise/clockwise
(CCW/CW)
• Select menu -1- (all parameters)
• Press "Enter" key
• Set code
• Press "Enter" key
• Set subcode C001
• Press "Enter" key
• Set value "01"
• Press "Enter" key
DI1
DI2
DI3
DI4
RFR
X4
24E
DO1
12I AR A1U GND
0
10V
...
1k
10k
W
...
W
AR A1U GND
DI1
DI2
DI3
RFR
X4
DO1
12I
24E
DI4
-0-
_
`
PASS
5 sec.
0000
_
`
....
....
_
`
....
`
....
....
`
_
_
_
`
....
C002
c001
01
-1-
8888
Status
Password
Menu
Code
Subcode
Action