Firmware 03.00 - DMS EN 5.0 - 07/2009
L
133
8400 BaseLine D | Software Manual
Error management
Error messages of the operating system
7.5.4
Cause & possible remedies
This chapter contains all error messages of the controller operating system in numerical
order of the error number with detailed information on the response to the error message
as well as information on the cause & possible remedies.
Tip!
A list of all error messages of the controller operating system in alphabetical order
can be found in the previous chapter
Table of the individual errors
Subject area
Error no.
Error cause
Error
response
Remedy by the user
No.
Name
119
Temperature
7798785
OH: Heatsink overtemperature
The heatsink temperature is higher than the
fixed limit temperature (90 ° C).
The ambient temperature of the controller may
be too high or the fan or its ventilation slots may
be dirty.
1: Error -
pulse inhibit
("Fault")
Check control cabinet temperature.
Clean air filter of control cabinet
Clean controller.
If required, clean or replace the fan
Provide for sufficient cooling of the
device.
119
Temperature
7798834
OC5: Ixt overload
The Ixt overload check has tripped due to
1.) wrong dimensioning of the device with
regard to its motor load or
2.) non-compliance with the load cycles
Regarding 1.) Check and, if required,
correct the dimensioning between the
device and motor load with regard to
technical data
Regarding 2.) Reduce load cycles of the
motor.
Observe load cycles according to the
documentation.
123
Motor
management /
encoder
8060942
OU: DC-bus overvoltage
The device has detected an overvoltage in the DC
bus and an earth fault on the motor side. In order
to protect the device hardware, the inverter
control is switched off.
Depending on the configuration of the auto-
serves to set that, if
the this error has been tripped, the controller
only starts after the controller inhibit is
switched.
If this error message remains active longer than
the time set in
, a "Fault" is tripped.
2: Trouble
Reduction of the load in generator
mode.
Use of a brake resistor
Use of a regenerative power supply
module.
Layout of a DC-bus connection.
Remove earth fault on the motor side.
123
Motor
management /
encoder
8060943
LU: DC-bus undervoltage
The device has detected an undervoltage in the
DC bus. The inverter control is switched off since
the drive characteristics of the motor control
cannot be ensured anymore due to the DC-bus
undervoltage. The configuration of the auto-
start lock function
serves to set that,
after this error has tripped, the controller only
starts after the controller inhibit is switched.
2: Trouble
Switch on the mains supply or ensure
sufficient supply via DC bus.
Adapt
, if required
123
Motor
management /
encoder
8060944
OC1: Power section - short circuit
The device has detected a short circuit of the
motor phases. In order to protect the device
electronics, the inverter control is switched off.
Mostly, faulty motor connections are the reason.
If the device is dimensioned inappropriately with
regard to the motor load and if the current
limitation in the current controller is
misadjusted (I
max
controller), this error message
may occur as well.
See also the chapter Motor control - defining
current limits
1: Error -
pulse inhibit
("Fault")
Check of the motor connections and
the corresponding plug connector at
the device.
Compliance with the permissible
combinations of device and motor
power.
Do not set the dynamics of the current
limitation controller too high.