Parameter reference
Parameter list | C00142
C00142
C00144
Parameter | Name:
C00142 | Auto-start option
Data type: UNSIGNED_8
Index: 24433
d
= 5F71
h
Setting of the "Auto-start" function
• When inhibit is activated, the motor can only start after the device state has changed.
Setting range
(min. hex value | max. hex value)
Lenze setting
0x00
0xFF
0x01
(decimal: 1)
Value is bit-coded: (
;
= bit set)
Bit 0
;
Inhibit at power-on
Bit 1
Inhibit at trouble
Bit 2
Inhibit at fault
Bit 3
Reserved
Bit 4
Reserved
Bit 5
Reserved
Bit 6
Reserved
Bit 7
Reserved
;
Read access
;
Write access
CINH
PLC STOP
No transfer
COM
MOT
Parameter | Name:
C00144 | Switching freq. reduct. (temp.)
Data type: UNSIGNED_8
Index: 24431
d
= 5F6F
h
Activation of the automatic switching frequency reduction at too high temperature
Selection list
(Lenze setting printed in bold)
Info
0 Off
Automatic switching frequency reduction deactivated
1 On
Automatic switching frequency reduction activated
;
Read access
;
Write access
CINH
PLC STOP
No transfer
COM
MOT
Scaling factor: 1