8400 BaseLine D | Software Manual
Parameter reference
Parameter list | C00064
184
L
Firmware 03.00 - DMS EN 5.0 - 07/2009
C00064
C00066
C00073
C00074
C00081
Parameter | Name:
C00064 | Device utilisation (Ixt)
Data type: INTEGER_16
Index: 24511
d
= 5FBF
h
Display of the device utilisation Ixt in different time resolutions
• If the value displayed here exceeds the threshold set in
, the fault message "OC5: Device overload (Ixt)"
is output and the fault response set in
is executed (default setting: "Warning").
Display range
(min. value | unit | max. value)
0
%
250
Subcodes
Info
C00064/1
Device utilisation (Ixt)
• Maximum value of the pulse utilisation (C00064/2)
and permanent utilisation (C00064/3).
C00064/2
Device utilisation (Ixt) 15s
• Pulse utilisation via the last 15 seconds (only for loads
>160 %).
C00064/3
Device utilisation (Ixt) 3min
• Permanent utilisation via the last 3 minutes.
;
Read access
Write access
CINH
PLC STOP
;
No transfer
COM
MOT
Scaling factor: 100
Parameter | Name:
C00066 | Thermal motor load (I²xt)
Data type: INTEGER_16
Index: 24509
d
= 5FBD
h
Display of the thermal motor load being detected sensorless via a motor model
• If the value displayed here exceeds the threshold set in
, the fault message "OC6: Device overload (Ixt)"
is output and the fault response set in
is executed (default setting: "Warning").
Display range
(min. value | unit | max. value)
0
%
200
;
Read access
Write access
CINH
PLC STOP
;
No transfer
COM
MOT
Scaling factor: 100
Parameter | Name:
C00073 | Vp Imax controller
Data type: UNSIGNED_16
Index: 24502
d
= 5FB6
h
Gain factor Vp for Imax controller
Setting range
(min. value | unit | max. value)
Lenze setting
0.00
16.00
0.25
;
Read access
;
Write access
CINH
PLC STOP
No transfer
COM
;
MOT
Scaling factor: 100
Parameter | Name:
C00074 | Ti Imax controller
Data type: UNSIGNED_16
Index: 24501
d
= 5FB5
h
Reset time Ti for Imax controller
Setting range
(min. value | unit | max. value)
Lenze setting
12
ms
9990
65 ms
;
Read access
;
Write access
CINH
PLC STOP
No transfer
COM
;
MOT
Scaling factor: 1
Parameter | Name:
C00081 | Rated motor power
Data type: UNSIGNED_16
Index: 24494
d
= 5FAE
h
This value can be obtained from the motor nameplate. After the motor to be used has been selected from the motor
catalogue, the suitable value can be entered automatically.
Note:
It is mandatory to give the rated motor power for the field-oriented operating mode (SLVC).
Setting range
(min. value | unit | max. value)
Lenze setting
0.00
kW
99.00
11.00 kW
;
Read access
;
Write access
CINH
PLC STOP
No transfer
COM
;
MOT
Scaling factor: 100