Firmware 03.00 - DMS EN 5.0 - 07/2009
L
181
8400 BaseLine D | Software Manual
Parameter reference
Parameter list | C00029 |
C00029 |
C00033 |
C00034 |
C00036
Parameter | Name:
C00029 | AINx: Input current
Data type: INTEGER_16
Index: 24546
d
= 5FE2
h
Display of the input current at the analog input
• When the analog input is configured for current measurement (
= 1 or 2).
• When
is set = 2 (4 ... 20 mA), 0 ... 16 mA is displayed.
Display range
(min. value | unit | max. value)
0.0
mA
20.0
Subcodes
Info
C00029/1
AIN1: Input current
;
Read access
Write access
CINH
PLC STOP
;
No Transfer
COM
MOT
Scaling factor: 100
Parameter | Name:
C00033 | AINx: Output value
Data type: INTEGER_16
Index: 24542
d
= 5FDE
h
Display of the output value in percent of the analog input amplifier
• 100 %
≡
16384
≡
+10 V / +20 mA
Display range
(min. value | unit | max. value)
-199.9
%
199.9
Subcodes
Info
C00033/1
AIN1: Output value
;
Read access
Write access
CINH
PLC STOP
;
No Transfer
COM
MOT
Scaling factor: 100
Parameter | Name:
C00034 | AINx: Configuration
Data type: UNSIGNED_8
Index: 24541
d
= 5FDD
h
Configuration of the analog input for current or voltage measurement
Selection list
Info
0 0...+10 V
Input signal is the voltage signal 0 V ... +10 V
• 0 V ... +10 V
≡
0 % ... +100 %
1 0...+5V
With external load resistor (250 Ohms):
Input signal is the current signal 0 mA ... 20 mA
• 0 mA ... 20 mA
≡
0 % ... +100 %
2 1...+5V (4...20mA)
With external load resistor (250 Ohms):
Input signal is the current signal 4 mA ... 20 mA
• 4 mA ... 20 mA
≡
0 % ... +100 %
• The current loop is monitored for open circuit
(I < 4 mA) by the device .
Subcodes
Lenze setting
Info
C00034/1
0: 0...+10 V
AIN1: Config.
;
Read access
;
Write access
CINH
PLC STOP
No transfer
COM
MOT
Scaling factor: 1
Parameter | Name:
C00036 | DCB: Current
Data type: INTEGER_16
Index: 24539
d
= 5FDB
h
Current value in [%] for DC-injection braking
• 100 %
≡
Imax in motor mode (
)
Setting range
(min. value | unit | max. value)
Lenze setting
0.0
%
150.0
50.0 %
;
Read access
;
Write access
CINH
PLC STOP
No transfer
COM
MOT
Scaling factor: 100