8400 BaseLine D | Software Manual
Parameter reference
Parameter list | C00106
188
L
Firmware 03.00 - DMS EN 5.0 - 07/2009
C00106
C00107
C00114
Parameter | Name:
C00106 | Auto-DCB: hold time
Data type: UNSIGNED_32
Index: 24469
d
= 5F95
h
Hold time of the automatic DC injection brake
• The DC injection brake is applied for the time set here if the value falls below the speed setpoint set in
Setting range
(min. value | unit | max. value)
Lenze setting
0.0
s
999.0
0.5 s
;
Read access
;
Write access
CINH
PLC STOP
No transfer
COM
MOT
Scaling factor: 1000
Parameter | Name:
C00107 | DCB: hold time
Data type: UNSIGNED_32
Index: 24468
d
= 5F94
h
Maximum hold time of the manual DC injection brake
• In order to not overload the motor thermally, a time for automatic switch-off of the DC injection brake can be set
here.
Setting range
(min. value | unit | max. value)
Lenze setting
0.0
s
999.0
999.0 s
;
Read access
;
Write access
CINH
PLC STOP
No transfer
COM
MOT
Scaling factor: 1000
Parameter | Name:
C00114 | DIx inversion
Data type: UNSIGNED_16
Index: 24461
d
= 5F8D
h
Polarity of the digital inputs
• Every digital input of the device can be inverted with regard to polarity via this bit field.
Setting range
(min. hex value | max. hex value)
Lenze setting
0x0000
0xFFFF
0x8000
(decimal: 32768)
Value is bit-coded: (
;
= bit set)
Info
Bit 0
DI1 inverted
Inversion of digital input 1
Bit 1
DI2 inverted
Inversion of digital input 2
Bit 2
DI3 inverted
Inversion of digital input 3
Bit 3
DI4 inverted
Inversion of digital input 4
Bit 4
Reserved
Bit 5
Reserved
Bit 6
Reserved
Bit 7
Reserved
Bit 8
Reserved
Bit 9
Reserved
Bit 10
Reserved
Bit 11
Reserved
Bit 12
Reserved
Bit 13
Reserved
Bit 14
Reserved
Bit 15
;
RFR inverted
Inversion of digital input CInh (controller inhibit)
;
Read access
;
Write access
CINH
PLC STOP
No transfer
COM
MOT