Firmware 03.00 - DMS EN 5.0 - 07/2009
L
201
8400 BaseLine D | Software Manual
Parameter reference
Parameter list | C00242
C00242
C00243
C00244
C00245
Parameter | Name:
C00242 | L_PCTRL_1: operating mode
Data type: UNSIGNED_8
Index: 24333
d
= 5F0D
h
From version 03.00.00
FB
: Selection of the operating mode
• Depending on the selection, the blue switches in the displayed signal flow are set accordingly in the Engineer on
the
Application parameter
tab in the
Overview
Signal flow
Process controller
dialog level.
Selection list
(Lenze setting printed in bold)
Info
0 Off
The input setpoint
nNSet_a
is output without any chang-
es at the
nOut_a
output.
1 Ad feedforward control
nNSet_a
and
nAct_a
are used as PID input values. The in-
put setpoint
nNSet_a
is added to the value output by the
PID element.
2 PID as setpoint generator
nSet_a
and
nAct_a
are used as PID input values. The
nNSet_a
input is not considered.
3 PID setpoint from L_NSet_1
nNSet_a
and
nAct_a
are used as PID input values. The
nSet_a
is not considered.
;
Read access
;
Write access
CINH
PLC STOP
No transfer
COM
MOT
Scaling factor: 1
Parameter | Name:
C00243 | L_PCTRL_1: Acceleration time influence
Data type: UNSIGNED_32
Index: 24332
d
= 5F0C
h
From version 03.00.00
FB
: Acceleration time for showing the PID output value
Setting range
(min. value | unit | max. value)
Lenze setting
0.0
s
999.9
5.0 s
;
Read access
;
Write access
CINH
PLC STOP
No transfer
COM
MOT
Scaling factor: 1000
Parameter | Name:
C00244 | L_PCTRL_1: Deceleration time influence
Data type: UNSIGNED_32
Index: 24331
d
= 5F0B
h
From version 03.00.00
FB
: Deceleration time for masking out the PID output value
Setting range
(min. value | unit | max. value)
Lenze setting
0.0
s
999.9
5.0 s
;
Read access
;
Write access
CINH
PLC STOP
No transfer
COM
MOT
Scaling factor: 1000
Parameter | Name:
C00245 | L_PCTRL_1: PID output value
Data type: INTEGER_16
Index: 24330
d
= 5F0A
h
From version 03.00.00
FB
: Display of the output value of the PID process controller
Display range
(min. value | unit | max. value)
-199.9
%
199.9
;
Read access
Write access
CINH
PLC STOP
No transfer
COM
MOT
Scaling factor: 100