8400 BaseLine D | Software Manual
Parameter reference
Parameter list | C00118
C00118
C00120
C00123
C00134
Parameter | Name:
C00118 | DOx inversion
Data type: UNSIGNED_8
Index: 24457
d
= 5F89
h
Polarity of the digital outputs
• Every digital output of the device can be inverted with regard to polarity via this bit field.
Setting range
(min. hex value | max. hex value)
Lenze setting
0x00
0xFF
0x00
(decimal: 0)
Value is bit-coded: (
;
= bit set)
Info
Bit 0
Relay inverted
Relay inversion
Bit 1
DO1 inverted
Inversion of digital output 1
Bit 2
Reserved
Bit 3
Reserved
Bit 4
Reserved
Bit 5
Reserved
Bit 6
Reserved
Bit 7
Reserved
;
Read access
;
Write access
CINH
PLC STOP
No transfer
COM
MOT
Parameter | Name:
C00120 | Motor overload threshold (I²xt)
Data type: INTEGER_16
Index: 24455
d
= 5F87
h
Operating threshold for the error message "OC6: Motor overload (I²xt)"
• The response for reaching the threshold can be selected in
• The current thermal motor load is displayed in
Setting range
(min. value | unit | max. value)
Lenze setting
0
%
250
100 %
;
Read access
;
Write access
CINH
PLC STOP
No transfer
COM
MOT
Scaling factor: 100
Parameter | Name:
C00123 | Device utilisat. threshold (Ixt)
Data type: INTEGER_16
Index: 24452
d
= 5F84
h
Operating threshold for the error message "OC5: Device overload (Ixt)"
• The response for reaching the threshold can be selected in
• The current device utilisation is displayed in
Setting range
(min. value | unit | max. value)
Lenze setting
0
%
100
100 %
;
Read access
;
Write access
CINH
PLC STOP
No transfer
COM
MOT
Scaling factor: 100
Parameter | Name:
C00134 | Ramp smoothing main setpoint
Data type: UNSIGNED_8
Index: 24441
d
= 5F79
h
Configuration of the ramp rounding for the main setpoint
Selection list
(Lenze setting printed in bold)
Info
0 Off
Ramp rounding deactivated
1 PT1 behaviour
Ramp rounding with PT1 behaviour
• The corresponding S-ramp time must be set in
;
Read access
;
Write access
CINH
PLC STOP
No transfer
COM
MOT
Scaling factor: 1