8400 StateLine C | Reference manual
Parameter reference
Parameter list | C00342
580
L
Firmware
≤
11.00 - DMS 8.0 EN - 10/2011
C00342
Parameter | Name:
C00342 | CAN decoupling PDOInOut
Data type: UNSIGNED_16
Index: 24233
d
= 5EA9
h
From version 04.00.00
Configuration defining the events that lead to a decoupling of the process data words.
Configuring exception handling of the CAN PDOs
Setting range
(min. hex value | max. hex value)
0x0000
0xFFFF
Value is bit-coded: (
;
= bit set)
Bit 0
BusOff_MsgErr
Bit 1
Warning
Bit 2
NodeStopped
Bit 3
HeartBeatEvent
Bit 4
CAN1_In_Überw.
Bit 5
CAN2_In_Überw.
Bit 6
CAN3_In_Überw.
Bit 7
Reserved
Bit 8
Reserved
Bit 9
Reserved
Bit 10
Reserved
Bit 11
Reserved
Bit 12
Reserved
Bit 13
Reserved
Bit 14
Trouble
Bit 15
Fault
Subcodes
Lenze setting
Info
C00342/1
0
CAN decoupling PDO_In from the bus
C00342/2
0
CAN decoupling PDO_Out from the appl.
;
Read access
;
Write access
CINH
PLC STOP
No transfer
COM
MOT