Firmware
≤
11.00 - DMS 8.0 EN - 10/2011
L
483
8400 StateLine C | Reference manual
System bus "CAN on board"
Implemented CANopen objects
I-1016
Monitoring time for the nodes to be monitored via heartbeat.
Heartbeat protocol
(
471)
The parameterised time is rounded down to an integer multiple of 5 ms and must have
a greater value than the heartbeat producer time of the node to be monitored.
[10-4] Data telegram assignment
Index:
I-1016
Name:
Consumer heartbeat time
Subindex
Default setting
Setting range (min. value | unit | max. value)
Access
Data type
0: Highest subindex supported
1 (for BaseLine)
7 (for StateLine)
15 (from HighLine
onwards)
- (read access only)
ro
U16
1 ... n: Consumer heartbeat time
0
0
65535 rw
U16
Subindex
Meaning
Lenze code
0
Number of nodes to be monitored
1 ... n
Node ID and heartbeat time of the node to be monitored Node ID:
C00385/x
Heartbeat time:
C00386/x
8th byte
7th byte
6th byte
5th byte
Data 4
Data 3
Data 2
Data 1
Bit 31 ... bit 24
Bit 23 ... Bit 16
Bit 15 ... Bit 0
0
(Reserved)
Node ID
Heartbeat time