Firmware
≤
11.00 - DMS 8.0 EN - 10/2011
L
497
8400 StateLine C | Reference manual
System bus "CAN on board"
Implemented CANopen objects
I-1A00
The object I-1A00 serves to send parameter data as TPDO1.
This object relates to code
C00868/1...4
.
[10-16] Data telegram assignment
IEC 61131 process data words are mapped. Only whole bytes can be mapped (1-
byte/mapping entry).
Related topics:
TPDO1 | Port block "LP_CanOut1"
(
447)
I-1A01
The object I-1A01 serves to send parameter data as TPDO2.
This object relates to code
C00868/5...8
.
For data telegram assignment, see object
I-1A00
.
Related topics:
TPDO2 | Port block "LP_CanOut2"
(
448)
Index:
I-1A00
Name:
TPDO1 mapping parameter
Subindex
Default setting
Setting range (min. value | unit | max. value)
Access
Data type
0: Number of mapped application
objects in PDO
0
0
8 rw
U8
1 ... 4: Application object 1 ... 4
0
0
4294967295 rw
U32
Subindex
Meaning
0
Number of mapped objects
1 ... 4
Mapping entries 1 ... 4 for TPDO1
• The 4th mapping entry is used for the statistic mapping. For this, there is no value
available.
8th byte
7th byte
6th byte
5th byte
Data 4
Data 3
Data 2
Data 1
Bit 31 ... bit 16
Bit 15 ... bit 8
Bit 7 ... bit 0
Index
Subindex
Length
Index:
I-1A01
Name:
TPDO2 mapping parameter
Subindex
Default setting
Setting range (min. value | unit | max. value)
Access
Data type
0: Number of mapped application
objects in PDO
0
0
8 rw
U8
1 ... 4: Application object 1 ... 4
0
0
4294967295 rw
U32
Subindex
Meaning
0
Number of mapped objects
1 ... 4
Mapping entries 1 ... 4 for TPDO2
• The 4th mapping entry is used for the statistic mapping. For this, there is no value
available.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]