8400 StateLine C | Reference manual
Parameter reference
Parameter list | C00079
542
L
Firmware
≤
11.00 - DMS 8.0 EN - 10/2011
C00079
C00080
C00081
C00082
Parameter | Name:
C00079 | SC: Settings
Data type: UNSIGNED_8
Index: 24496
d
= 5FB0
h
Configuration of various options for sensorless control for synchronous motors (
SLPSM
)
Selection list
0 Off
1 On
Subcodes
Lenze setting
Info
C00079/1
0: Off
SC: Current controller - feedforward control
• Feedforward control/decoupling network of the
current controller.
C00079/2
1: On
SC: Adapt. field weakening controller
• Speed-dependent adaptive field weakening
controller.
C00079/3
0: Off
SC: n-Ctrl Anti-Wind-Up
• "Anti-wind-up" effect of the speed controller in case
of an output voltage limitation in the field weakening
range.
C00079/4
1: On
Field weakening for synchronous motors
•
From version 11.00.00
;
Read access
;
Write access
CINH
PLC STOP
No transfer
COM
;
MOT
Scaling factor: 1
Parameter | Name:
C00080 | Override point of field weakening
Data type: INTEGER_16
Index: 24495
d
= 5FAF
h
Offset of the override point of field weakening
• In the V/f characteristic control mode (
VFCplus
), the stall protection function or the max. permissible current in
the field weakening range can be adapted.
Setting range
(min. value | unit | max. value)
Lenze setting
-500
Hz
500
0 Hz
;
Read access
;
Write access
CINH
PLC STOP
No transfer
COM
;
MOT
Scaling factor: 1
Parameter | Name:
C00081 | Rated motor power
Data type: UNSIGNED_16
Index: 24494
d
= 5FAE
h
This value can be obtained from the motor nameplate. After the motor to be used has been selected from the motor
catalogue, the suitable value can be entered automatically.
Note:
It is mandatory to give the rated motor power for the sensorless vector control (
SLVC
).
Setting range
(min. value | unit | max. value)
Lenze setting
0.00
kW
500.00
11.00 kW
;
Read access
;
Write access
CINH
PLC STOP
No transfer
COM
;
MOT
Scaling factor: 100
Parameter | Name:
C00082 | Motor rotor resistance
Data type: UNSIGNED_32
Index: 24493
d
= 5FAD
h
After the motor to be used has been selected from the motor catalogue, the suitable value can be entered
automatically. An automatic detection via the motor parameter identification is possible as well.
Setting range
(min. value | unit | max. value)
Lenze setting
0
mOhm
200000
276 mOhm
;
Read access
;
Write access
CINH
PLC STOP
No transfer
COM
;
MOT
Scaling factor: 1