8400 StateLine C | Reference manual
Technology applications
TA "Actuating drive speed"
7.2.4
Process data assignment for fieldbus communication
The fieldbus communication is connected (preconfigured) to the previously selected
technology application by selecting the corresponding control mode in
C00007
:
"30:
CAN
" for the connection to the system bus (CAN)
"40:
MCI
" for the connection to a plugged-on communication module (e.g. PROFIBUS)
The assignment of the process data words does not depend on the applied bus system but
exclusively on the application:
Input words
Name
Assignment
Word 1 DriveControl
Control word
• See table below for bit assignment.
Word 2 MainSetValue
Speed setpoint
• Scaling: 16384
≡
100 % reference speed (
C00011
)
Word 3 -
Not preconfigured
Word 4 -
Not preconfigured
Word 5 ... 16 -
Not preconfigured
• Only available for control mode "40: MCI".
Control word
Name
Function
Bit 0 SwitchOn
1
≡
Change to the "
SwitchedOn
" device status
• This bit must be set in the CAN/MCI control word to ensure
that the device changes to the "
SwitchedOn
" device status
after mains connection without the need for a master control
specifying this bit via fieldbus.
• If control via a bus system is not wanted (e.g. in the case of
control via terminals), the
wDriveCtrl
output signal of the
LS_ParFix
system block can be connected to the control word
inputs.
Bit 1 DisableVoltage
1
≡
Inhibit inverter control (IMP - pulse inhibit)
Bit 2 SetQuickStop
1
≡
Activate quick stop (QSP).
Activate/Deactivate quick stop (
83)
Bit 3 EnableOperation
1
≡
Enable controller (RFR)
• If control via terminals is performed, this bit must be set both
in the CAN control word and in the MCI control word.
Otherwise, the controller is inhibited.
Enable/Inhibit controller (
82)
Bit 4 ModeSpecific_1
Reserved (currently not assigned)
Bit 5 ModeSpecific_2
Bit 6 ModeSpecific_3
Bit 7 ResetFault
1
≡
Reset fault (trip reset)
• Acknowledge fault message (if the error cause has been
eliminated).
Reset error (
84)
Bit 8 SetHalt
1
≡
Activate stop function
• Stop drive via stopping ramp (in preparation).
Bit 9 reserved_1
Reserved (currently not assigned)
Bit 10 reserved_2
Bit 11 SetDCBrake
1
≡
Activate DC-injection braking
Manual DC-injection braking (DCB) (
204)
Bit 12 JogSpeed1
Activation of fixed speed 1 ... 3
Bit 13 JogSpeed2