Firmware
≤
11.00 - DMS 8.0 EN - 10/2011
L
543
8400 StateLine C | Reference manual
Parameter reference
Parameter list | C00083
C00083
C00084
C00085
C00087
C00088
Parameter | Name:
C00083 | Motor rotor time constant
Data type: UNSIGNED_16
Index: 24492
d
= 5FAC
h
From version 02.00.00
Display of the rotor time constant of the motor
• This value is calculated from the rotor resistance and the rotor inductance (leakage and magnetising
inductance).
Display range
(min. value | unit | max. value)
0
ms
32767
;
Read access
Write access
CINH
PLC STOP
;
No transfer
COM
MOT
Scaling factor: 1
Parameter | Name:
C00084 | Motor stator resistance
Data type: UNSIGNED_32
Index: 24491
d
= 5FAB
h
After the motor to be used has been selected from the motor catalogue, the suitable value can be entered
automatically. An automatic detection via the motor parameter identification is possible as well.
Setting range
(min. value | unit | max. value)
Lenze setting
0
mOhm
200000
330 mOhm
;
Read access
;
Write access
CINH
PLC STOP
No transfer
COM
;
MOT
Scaling factor: 1
Parameter | Name:
C00085 | Motor stator leakage inductance
Data type: UNSIGNED_16
Index: 24490
d
= 5FAA
h
After the motor to be used has been selected from the motor catalogue, the suitable value can be entered
automatically. An automatic detection via the motor parameter identification is possible as well.
Setting range
(min. value | unit | max. value)
Lenze setting
0.00
mH
650.00
3.50 mH
;
Read access
;
Write access
CINH
PLC STOP
No transfer
COM
;
MOT
Scaling factor: 100
Parameter | Name:
C00087 | Rated motor speed
Data type: UNSIGNED_16
Index: 24488
d
= 5FA8
h
This value can be obtained from the motor nameplate. After the motor to be used has been selected from the motor
catalogue, the suitable value can be entered automatically.
Note:
It is mandatory to give the rated motor speed for the sensorless vector control (
SLVC
).
Setting range
(min. value | unit | max. value)
Lenze setting
50
rpm
60000
1460 rpm
;
Read access
;
Write access
CINH
PLC STOP
No transfer
COM
;
MOT
Scaling factor: 1
Parameter | Name:
C00088 | Rated motor current
Data type: UNSIGNED_16
Index: 24487
d
= 5FA7
h
This value can be obtained from the motor nameplate. After the motor to be used has been selected from the motor
catalogue, the suitable value can be entered automatically.
Setting range
(min. value | unit | max. value)
Lenze setting
0.20
A
320.00
21.00 A
;
Read access
;
Write access
CINH
PLC STOP
No transfer
COM
;
MOT
Scaling factor: 100