8400 StateLine C | Reference manual
Parameter reference
Parameter list | C00034
536
L
Firmware
≤
11.00 - DMS 8.0 EN - 10/2011
C00034
C00036
C00039
Parameter | Name:
C00034 | AINx: Configuration
Data type: UNSIGNED_8
Index: 24541
d
= 5FDD
h
Configuration of the analog input for current or voltage measurement
Analog terminals
Selection list
Info
0 -10...+10 V
Input signal is the voltage signal -10 V ... +10 V
• -10 V ... +10 V
≡
-100 % ... +100 %
1 0...20 mA
Input signal is the current signal 0 mA ... 20 mA
• 0 mA ... 20 mA
≡
0 % ... +100 %
2 4...20 mA
Input signal is the current signal 4 mA ... 20 mA
• 4 mA ... 20 mA
≡
0 % ... +100 %
• The current loop is monitored for open circuit
(I < 4 mA) by the device.
Subcodes
Lenze setting
Info
C00034/1
0: -10...+10 V
AIN1: Config.
;
Read access
;
Write access
CINH
PLC STOP
No transfer
COM
MOT
Scaling factor: 1
Parameter | Name:
C00036 | DC braking: Current
Data type: INTEGER_16
Index: 24539
d
= 5FDB
h
Braking current in [%] based on rated device current (
C00098
)
DC-injection braking
Setting range
(min. value | unit | max. value)
Lenze setting
0.00
%
200.00
50.00 %
;
Read access
;
Write access
CINH
PLC STOP
No transfer
COM
MOT
Scaling factor: 100
Parameter | Name:
C00039 | Fixed setpoint x (L_NSet_1 n-Fix)
Data type: INTEGER_16
Index: 24536
d
= 5FD8
h
The
L_NSet_1
FB: Fixed speed setpoints (JOG values) for the setpoint generator
Setting range
(min. value | unit | max. value)
-199.99
%
199.99
Subcodes
Lenze setting
Info
C00039/1
40.00 %
Fixed setpoint 1
C00039/2
60.00 %
Fixed setpoint 2
C00039/3
80.00 %
Fixed setpoint 3
C00039/4
0.00 %
Fixed setpoint 4
C00039/5
0.00 %
Fixed setpoint 5
C00039/6
0.00 %
Fixed setpoint 6
C00039/7
0.00 %
Fixed setpoint 7
C00039/8
0.00 %
Fixed setpoint 8
C00039/9
0.00 %
Fixed setpoint 9
C00039/10
0.00 %
Fixed setpoint 10
C00039/11
0.00 %
Fixed setpoint 11
C00039/12
0.00 %
Fixed setpoint 12
C00039/13
0.00 %
Fixed setpoint 13
C00039/14
0.00 %
Fixed setpoint 14
C00039/15
0.00 %
Fixed setpoint 15
;
Read access
;
Write access
CINH
PLC STOP
No transfer
COM
MOT
Scaling factor: 100
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]