10: Remote Power Managers
EMG™ Edge Management Gateway User Guide
201
3. To save, click
Apply
.
Log Status
Indicates if the status of the RPM is periodically logged. Select Yes, minutes to log
the status periodically and enter a value between 1 and 60 minutes. The logs can be
viewed by viewing the RPMs web page and clicking on "Logs".
Critical SNMP Traps
If enabled, under critical conditions (UPS goes onto battery power, UPS battery is
low, UPS forced shutdown in progress, UPS on line power, UPS battery needs to be
replaced, RPM is unavailable, communications with RPM lost, communications with
RPM established), a slcEventRPMAction trap will be sent to the NMS configured in
settings. This requires that SNMP traps be enabled.
Critical Emails
If an email address is specified, under critical conditions (see Critical SNMP Traps
above), an email notification will be sent to the email address. The Server and
settings will be used to send the email.
Low Battery
For UPS devices only. Indicates the behavior to take when the UPS reaches a low
battery state. Options are to Shutdown this UPS - shutdown only the UPS that has
reached a low battery state; Shutdown all UPSes - shutdown all UPSes managed by
the EMG; Allow battery failure - allow the battery to completely fail, which may result
in the unsafe shutdown of the devices it provides power to; Shutdown both EMG
UPSes - shutdown both UPSes that provide power to the EMG, including the UPS
with that has reached a low battery state (some EMGs have dual power supplies).
For more information, see
Shutdown Order
For UPS devices only. If any of the UPSes managed by the EMG reaches a low
battery state AND is configured for Shutdown all UPSes for its Low Battery setting,
this indicates the order in which this UPS will be shutdown. All UPSes with a
shutdown order of "1" will be shutdown first, followed by all UPSes with a shutdown
order of "2", etc. Shutdown orders are in the range of 1 to 49, with 50 being reserved
for UPSes that provide power to the EMG - they will always be shutdown last (see
Provides EMG Power
in the next field below).
Provides EMG
Power
For UPS devices only. Indicates if this UPS provides power to the EMG.