SIMBOL
SCREEN MESSAGE
MEANING
SOLUTION
RESET SOFTWARE
Generic malfunction that caused a reset of
the microcontroller.
There is an automatic recovery system in case of
temporary malfunction.
OBSTACLE IN OPENING
The door detect an obstacle during the
opening cycle that caused the reversal
direction of the leaf.
If the problem persists, check if there is any obstacle
that stop the door and remove it, or control the
smoothness of the leaf.
OBSTACLE IN CLOSING
The door detect an obstacle during the
closing cycle that caused the reversal
direction of the leaf.
If the problem persists, check if there is any obstacle
that stop the door and remove it, or control the
smoothness of the leaf.
RESET 4 OBSTACLE
IN CLOSING
If, during closing, the door detect an obstacle
at the same point for 4 consecutive times, a
reset occurs with subsequent opening at
slow speed.
Remove the obstacle that prevents the complete
closure of the door.
SIMBOL
SCREEN MESSAGE
MEANING
SOLUTION
FAULT CURRENT
The cyclical testing of the detection circuit
current has failed.
The system automatically resets and, after a few seconds,
repeat again the test. If the problem persists it is a defect
on the logic board L-NEP.
FAULT POWER
The control of the driving signal of the motor
has detected a fault.
The system automatically resets and, after a few seconds,
repeat again the test. If the problem persists it is a defect
on the logic board L-NEP.
ERROR INITIAL SET UP
The operator is not able to finish the initial
set-up.
Control the smoothness of the door and that there are
no obstacles along the way, that motor and encoder
are connected and try again to set-up the door.
ERROR ENCODER
OR MOTOR
Encoder signals are not detected or the
motor does not turn.
Check that the cables and connector of the motor and
encoder are well inserted and not damaged.
FAULT ENCODER
Fault detected during the test operation of
the encoder.
The system automatically resets, and repeat again the
test at the first cycle. If the problem persists it is a defect
on the logic board L-NEP.
ERROR SAFETY SENSOR
IN OPENING
The test on the safety opening sensor is failed.
Verify that the settings and parameters related to the
safety sensor test are correct, on the operator and on
the sensor.Also check that the electrical connection
between the sensor and controller are correct.
ERROR SAFETY SENSOR
IN CLOSING
The test on the safety closing sensor is failed.
Verify that the settings and parameters related to the
safety sensor test are correct, on the operator and on
the sensor.Also check that the electrical connection
between the sensor and controller are correct.
FAULT BRAKING
The control of the braking during closing cycle
has detected a fault.
The system automatically resets and repeat again the test
in every cycle. If the problem persists it is a defect on the
logic board L-NEP.
FAULT EEPROM REGISTER
The test of the internal memory cells related to
the safety parameter has failed.
The system automatically resets and, after a few seconds,
repeat again the test. If the problem persists it is a defect
on the logic board L-NEP.
ERROR COMMUNICATION
MASTER-SLAVE
The communication line between master
and slave is missing.
(with double door only)
Check that the WR5MS cable is connected between
master and slave and that the configuration setting for
double swing unit is correct.
GENERAL ERROR SLAVE
A fault is present on the slave operator.
(with double door only)
Access memory events on the slave operator and check
what type of problem is displayed.
MEMORY EVENTS
WARNINGS
ERRORS
Message of warnings or errors that can be read by digital programmer N-DSEL ( E1-E2-E3-E4-E5)