TERMINAL BOARD M3
Terminals 8-11
EXTERNAL RADAR input, N.O. contact.
It controls the door opening.
It is not active when the program selector is on “Exit only” and “Night lock”.
Terminals 9-11
INTERNAL RADAR input, N.O. contact.
It controls the door opening.
It is not active when the program selector is on “Entrance only” and “Night lock”.
Terminals 10-11
START input, N.O. contact.
It controls the door opening.
It is not active when the program selector is on “Night lock”.
TERMINAL BOARD M4
Connection of N-DSEL digital programmer.
Terminal 12 = - GND (power supply negative);
Terminal 13 = signal line A;
Terminal 14 = signal line B;
Terminal 15 = + 13V (power supply positive).
TERMINAL BOARD M6
Terminal 25
TEST output for safety sensors set for monitoring.
!
For more information, refer to "Safety sensors" paragraph.
Terminals 26-27
AUX 3 input, N.O. contact.
Unlocking the electric lock. A pulse on the
AUX3
input of the control unit unlocks the electric lock for 10 seconds to allow the opening of
the door by hand. As long as AUX3 input is activated the electric lock remains unlocked.
Terminals 28-29
Open Collector output of door status, it activates with open door and deactivates with closed door.
Connect a max. 100mA charge between 29 (O.C.) and 28 (po 24V) terminals.
!
In Interlock function (F26=ON), terminal 29 is used for connection of interlock operation; for more information, refer to “Interlock
system” paragraph.
TERMINAL BOARD M7
Terminals 16 (negative) - 17 (positive)
24Vdc output, max. 20W, for the power supply of control and safety sensors.
Led 2 ON indicates the proper operation of output.
TERMINAL BOARD M8
Terminals 18-19-20
Free contact of relay RL1 for electric lock connection; (18 = Common, 19 = N.O., 20 = N.C.).
Terminals 16 (negative) - 21 (positive)
24Vdc output for electric magnet or electric lock power supply.
!
For more information, refer to "Applications with electric lock" paragraph.
CONNECTORS
Connector J1 = transformer secondary (factory wiring).
Connector J2 = transformer primary (for 115V mains voltages).
Connector J3 = transformer primary (for 230V mains voltages, factory wiring).
Connector J4 = wiring of electric signals to connector J10 of L-NEP logic board.
Connector J5 = wiring of motor power supply to connector J11 of L-NEP logic board.
Led 1 ON indicates the presence of output voltage.
Connector J6 = connection with N-BAT battery module (see “N-BAT battery module”)