14) COMMISSIONING OF AUTOMATED DEVICE (INITIAL SET-UP)
After completing the mechanical installation and performing electric connections, manually shift the door leaf for its entire stroke, to ensure
that no friction appears on the movement.
SET-UP operation is compulsory to allow the operator electronic control unit to acquire stroke points.
When the set-up begins, the door must be closed and during the stroke learning cycle, no obstacle shall appear in the leaf movement area.
The NEPTIS SMP operator is equipped with a function allowing it to learn the position of the side wall during the initial set-up.
This function is useful as it allows to store the wall position at the end of the opening stroke, and as a consequence to precisely set the point
at which the tripping of the opening safety sensor causes the leaf to decelerate in the last few degrees of the opening stage.
It is important that you adjust the safety sensor detection field before starting the operator set-up cycle.
If Neptis SMP operator controls a single-leaf automatic door, dip 1 and 2 on SW1 dip-switch of L-NEP logic board must be set on OFF.
If two Neptis SMP operators must control a double-leaf automatic door, refer to “Double-leaf door set” paragraph..
Follow chapter 14.1 only if N-DSEL digital programmer is new and powered for the first time.
Follow chapter 14.2 if digital programmer has already been used before.
14.1) FIRST START OF N-DSEL DIGITAL PROGRAMMER
Power the Neptis SMP operator by mains voltage, the control unit buzzer emits some quick,
short beeps.
!
Language selection is shown on the display of N-DSEL digital programmer;
!
use
F2
and buttons to move the arrow in correspondence with the language desired.
!
Press EXIT button to exit “Language” section and enter “Serial communication
set-up” section, see paragraph14.3.
14.2)
USE OF N-DSEL DIGITAL PROGRAMMER
Power the Neptis SMP operator by mains voltage, the control unit buzzer emits some quick,
short beeps.
The display signals the lack of communication between N-DSEL and operator control units
since the serial code of L-NEP logic board is not stored on N-DSEL.
Press button for about 5 seconds to enter the general programming menu.
!
F1 button allows moving forward among menu symbols.
!
Select RS485 symbol.
!
Give a quick pulse to ENTER button to enter the “Serial communication setup”
section, see paragraph14.3.
14.3)
SERIAL COMMUNICATION SET-UP
N-DSEL programmer automatically detects the presence of operator electronic control unit (fig. A) and stores the serial code of L-NEP logic
board (fig. B).
When acquisition of serial code is completed, the display must show the closed padlock symbol on letter M and open padlock on letter S, for
a single leaf door (fig. C).
fig.A
fig.B
fig.C
For a double-leaf swing door, refer to “Double-leaf door set” paragraph.
Press EXIT button to exit “Serial communication set-up” section and enter the general programming menu.