26.3) FUNCTIONAL TESTING
Select the automatic operation of the door using the program selector.
If you use the manual switch, set the program at state
l.
Refer to par. "Program Selectors " that describe the types of selectors available to set the operating mode of the automatic doors.
To start an opening cycle give an impulse by the push-button PS1 (Start) on the module PWN-T of the Master operator, or operate the other
opening control devices ( as radar, mat, etc.).
Verify that opening and closing cycle takes place correctly.
During the opening cycle the Slave leaf start with a predetermined delay with
respect to Master leaf, as well as in the closing cycle is that the Master leaf that start with a predetermined delay with respect to Slave leaf.
The delay between the leaves at the start is crucial to avoid that it can come across each other. To change the preset delay door go to "Switch
and potentiometer" and set: On the parameter P19 the desired value of delay in opening ; on the parameter P20 the desired value of delay in
closing (see par. 17.2 "Parameters setting").
Verify that the input device and safety sensors are functioning; to adjust the detection range of the sensors, refer to the instructions supplied
with the sensor.
The detection of the opening safety sensor due to the arrest of the movement only of the leaf on which it is installed.
The detection of the closing safety sensor causes the inversion of the movement in opening of both doors.
During the movement of the door an intermittent buzzer sound may be hear. It's an indication that the limit power use by the operator it's near
the maximum available, Occur especially if the size and the weight of the leaf are approaching the limits permitted.
A short beep of the buzzer when leaf starting is to be considered normal because the inrush phase is the time in which it is required more
strength.
Adjust the power stroke with parameter P04 by the programmer N-DSEL (par.17.2 see "Parameters setting").
Power stroke P04 must be set on both master and slave operators separately (see par. 17 "Functions and regulation").
To turn off the audible buzzer that signal the power limit, set the F34 ON (see par. "Functions setting"), in this case independently on the two
operators.
The sound of the buzzer for almost the entire cycle means that the leaf exceeds the permissible limits, or that the installation dimensions
given in the drawings of installation have not been met, or that are present to much friction on the frame, in which case the automatic door
has difficulty moving and may fail to complete the cycle of opening and
Safety in case of impact: verify that opposing an obstacle to the movement of a door, the operator stop and reverse the direction of travel of
both doors
Every time, after powering the system, the first cycle of opening occurs at slow speed and can be selected with the function F31 if the leafs
starts together, or starts respecting the leaf delay.
F31 = OFF in the first cycle of opening the doors start together.
F31 = ON in the first cycle of opening the doors start, respecting the leaf delay.
It is recommended to keep the default setting (F31 OFF) if the door is not provided with coordinator mechanical closure, which guarantees
the correct position of the doors during the manual closure in the absence of power.
To set functions available see par. “Functions Setting”.
To adjust parameters see par. “Functions Setting”.
The operation of set-up must be repeated in the case of variation of one of the following conditions:
weight of the door, opening
angle of the leaf, spring loading, replacement of the logic board L-NEP or the mechanical unit inside the operator Neptis SMP.
To repeat the set-up, follow the steps described in the previous section. 26.2 (points 4, 5, 6).
26.4) PEDESTRIAN OPENING
With a double door it's possible to select the pedestrian opening, in which only Master operator open.
·
If is installed the program selector N-DSEL (F01 = ON), press the push-button to activate the pedestrian opening.
·
If is installed the manual selector switch or the mechanical key EV-MSEL (F01 = OFF), in order to activate the pedestrian opening is
necessary to set the
F15 = ON
.
Then you have to choose what position on the selector must be enabled pedestrian opening:
F16 = OFF
: pedestrian opening in position
0
on the manual selector program.
pedestrian opening in position on the mechanical selector EV-MSEL..
F16 = ON
: pedestrian opening in position
II
on the manual selector program.
pedestrian opening in position
on the mechanical selector EV-MSEL.
PEDESTRIAN OPENING WORKING MODE
Any opening activation via internal and external radars inputs and with the push push & go actuate partial opening of the door, then only the
leaf Master operate.
Any opening activation via Start, OPEN input and with the remote control Spyco combined with radio receiver EN/RF1
cause the complete opening of both doors.