B-2
BOP-1K 111315
B.2
NUMERICAL VALUES
For all
decimal
values the SCPI data parser of the BOP supports a maximum of eight digits after the decimal
point and a maximum of four digits before the decimal point. For example: If volt 10345.2e-1 is processed, the
output will become 34.52 volts because the unit only recognizes the first four digits preceding the decimal
point. Sending volt 0.0000034567e6 will result in the output being set to 3.45 volts because the unit only recog-
nizes the first eight digits after the decimal point.
The unit can process any number between 6500.9999 and.000001. Any values greater than these are not pro-
cessed by the device and a “120 - numeric data error” (see Table B-5) is generated. The largest string that can
be received or transmitted by the BOP is 253 characters. All numerical data is returned in scientific notation,
digits with decimal point and Exponent, e.g., 2.71E1 for 27.1.
The unit also supports keywords of MAXimum and MINImum to set the numeric entry to the most positive and
negative allowable values, respectively. For example, If the user has established the volt:limit to be 6, sending
the command VOLT MAX causes the output to be set to 6 volts. This syntax can be very useful in the setting of
a limit, e.g., VOLT:PROT:LIM MAX sets the positive voltage protection limit to the maximum voltage (E
O
max +
1%) and the negative voltage protection limit to (-1.01 x E
O
max).
B.3
ABORt COMMAND
ABOR
Syntax:
Short Form: ABOR
Long Form: ABORt
Description:
Cancels previously armed trigger, resets WTG.
if the trigger system is armed (INIT:CONT set to
OFF and INIT sent), sending ABORt disarms the trigger system so subsequent trigger commands
have no effect. If INIT:CONT ON has been programmed, this command has no effect. Related Com-
mands: INIT, *TRG. (See example, Figure B-1.)
B.4
CAL
COMMANDS AND QUERIES
CAL
CAL commands and queries are used to perform calibration of the unit via the control interface. These
commands must be issued in a specific sequence in order to properly calibrate the unit. To use these
commands, refer to Kepco’s website (www.kepcopower.com/drivers) and download the LabWindows/
CVI Version 5 driver for BOP or refer to PAR. 4.3. This file provides remote calibration capability and
uses the following supported commands and queries:
[SOUR:]VOLT:PROT:NEG, ?
B.101, B.102
SYST:COMM:SER:ECHO, ?
B.127, B.128
[SOUR:]VOLT:PROT:POS, ?
B.103, B.104
SYST:COMM:SER:PACE, ?
B.129, B.130
[SOUR:]VOLT:PROT:LIM[:BOTH], ?
B.105, B.106
SYST:COMM:SER:PROM, ?
B.131, B.132
[SOUR:]VOLT:PROT:LIM:NEG, ?
B.107, B.108
SYST:ERR?
B.133
[SOUR:]VOLT:PROT:LIM:POS, ?
B.109, B.110
SYST:ERR:CODE? ALL?
B.134, B.135
[SOUR:]VOLT:TRIG
B.111, B.112
SYST:KEYB, ?
B.136, B.137
STAT:OPER:COND?
B.113
SYST:PASS:CEN
B.138
STAT:OPER:ENAB, ?
B.114, B.115
SYST:PASS:CDIS
B.139
STAT:OPER[:EVEN]?
B.116
SYST:PASS:NEW
B.140
STAT:PRES
B.117
SYST:PASS:STAT
B.141
STAT:QUES[:EVEN]?
B.118
SYST:REM, ?
B.142, B.143
STAT:QUES:COND?
B.119
SYST:SEC:IMM
B.144
STAT:QUES:ENAB, ?
B.120, B.121
SYST:SET, ?
B.145, B.146
SYST:BEEP
B.122
SYST:VERS?
B.147
SYST:COMM:GPIB:ADDR, ?
B.123, B.124
TRIG:SOUR, ?
B.148, B.149
SYST:COMM:SER:BAUD, ?
B.125, B.126
TABLE B-1. SCPI SUBSYSTEM COMMAND/QUERY INDEX (CONTINUED)
COMMAND
PAR.
COMMAND
PAR.
NOTE: Commands listed above that are followed by “, ?“ have a related query.
Содержание BOP-MG 1KW
Страница 2: ......
Страница 10: ......
Страница 20: ...x BOP 1K 111315 FIGURE 1 1 HIGH POWER BOP SERIES POWER SUPPLY...
Страница 39: ...BOP HIPWR 111315 1 19 1 20 Blank FIGURE 1 3 BOP OUTPUT CHARACTERISTICS...
Страница 40: ......
Страница 56: ...2 16 BOP HIPWR 111315 FIGURE 2 5 PARALLEL CONFIGURATION LOCAL SENSING TYPICAL...
Страница 57: ...BOP HIPWR 111315 2 17 FIGURE 2 6 PARALLEL CONFIGURATION REMOTE SENSING TYPICAL...
Страница 68: ......