B-8
BOP-1K 111315
B.20
[SOURce:]CURRent[:LEVel][:IMMediate][:AMPlitude] QUERY
CURR?
Syntax:
Short Form: [SOUR:]CURR[:LEV][:IMM][:AMP]? MIN, MAX
Long Form: [SOURce:]CURRent[:LEVel][:IMMediate][:AMPlitude]? MIN, MAX
Return Value:
<exp_value> = digits with decimal point and Exponent, e.g., 2.71E1 for 27.1
Description:
Returns either the programmed value, maximum value, or minimum value of current.
The
CURR? query returns the programmed value of current. Actual output current will depend on load con-
ditions. The CURR?MAX query returns the maximum positive current allowed for a particular model.
CURR? MIN returns minimum negative current allowed for power supply (always negative).
Related
Commands:
CURR. (See example, Figure B-1.)
B.21
[SOURce:]CURRent[:LEVel]:LIMit[:BOTH] COMMAND
CURR:LIM[:BOTH]
Syntax:
Short Form: [SOUR:]CURR[:LEV]:LIM[:BOTH] <value>
Long Form: [SOURce:]CURRent[:LEVel]:LIMit[:BOTH] <value>
where <value> is between zero and I
NOM
Description: Establishes the software limit <value> for output current, i.e., sets the maximum value of output cur-
rent that the unit will be allowed to source and sink. Requires MEM:UPD (PAR. B.12) to save for
power up. See PAR. 3.5.2.2 and Figure 3-16 for special programming considerations. (See Figure B-
4)
B.22
[SOURce:]CURRent[:LEVel]:LIMit[:BOTH]? QUERY
CURR:LIM[:BOTH]?
Syntax:
Short Form: [SOUR:]CURR[:LEV]:LIM[:BOTH]?
Long Form: [SOURce:]CURRent[:LEVel]:LIMit[:BOTH]?
Returns <value>, <value>
Description: Identifies the positive software limit, followed by the negative software limit value of output current that
the unit can source or sink.
B.23
[SOURce:]CURRent[:LEVel]:LIMit:NEG COMMAND
CURR:LIM:NEG
Syntax:
Short Form: [SOUR:]CURR[:LEV]:LIM:NEG <value>
Long Form: [SOURce:]CURRent[:LEVel]:LIMit:NEGative <value>
Description: Establishes the negative software limit <value> for output current, i.e., sets the maximum value of out-
put current that the unit will be allowed to source (quadrant 3, Figure 1-3) or sink (quadrant 2) to the
value specified by the user. Requires MEM:UPD (PAR. B.12) to save for power up. See PAR. 3.5.2.2
and Figure 3-16 for special programming considerations.
B.24
[SOURce:]CURRent[:LEVel]:LIMit:NEG? QUERY
CURR:LIM:NEG?
Syntax:
Short Form: [SOUR:]CURR[:LEV]:LIM:NEG?
Long Form: [SOURce:]CURRent[:LEVel]:LIMit:NEGative?
Returns <value>
Description: Identifies the negative software limit value of output current that the unit can source (quadrant 3, Fig-
ure 1-3) or sink (quadrant 2).
B.25
[SOURce:]CURRent[:LEVel]:LIMit:POS COMMAND
CURR:LIM:POS
Syntax:
Short Form: [SOUR:]CURR[:LEV]:LIM:POS <value>
Long Form: [SOURce:]CURRent[:LEVel]:LIMit:POSitive <value>
where <value> is between zero and the rated (nominal) output voltage
Description: Establishes the positive software limit <value> for output current, i.e., sets the maximum value of out-
put current that the unit will be allowed to source (quadrant 1, Figure 1-3) or sink (quadrant 4) to the
value specified by the user. Requires MEM:UPD (PAR. B.12) to save for power up. See PAR. 3.5.2.2
and Figure 3-16 for special programming considerations.
Содержание BOP-MG 1KW
Страница 2: ......
Страница 10: ......
Страница 20: ...x BOP 1K 111315 FIGURE 1 1 HIGH POWER BOP SERIES POWER SUPPLY...
Страница 39: ...BOP HIPWR 111315 1 19 1 20 Blank FIGURE 1 3 BOP OUTPUT CHARACTERISTICS...
Страница 40: ......
Страница 56: ...2 16 BOP HIPWR 111315 FIGURE 2 5 PARALLEL CONFIGURATION LOCAL SENSING TYPICAL...
Страница 57: ...BOP HIPWR 111315 2 17 FIGURE 2 6 PARALLEL CONFIGURATION REMOTE SENSING TYPICAL...
Страница 68: ......