4-2
BOP-1K 111315
4.2
TEST EQUIPMENT REQUIREMENTS
Table 4-2 lists sense resistors recommended for measuring current and includes Kepco and
Manufacturer’s part numbers. The value of the sense resistor chosen should be known with
0.001% accuracy. If other than a recommended sense resistor is to be used, it must be rated for
at least 100W power dissipation (actual power dissipation will be approximately 10W). The ther-
mal coefficient of the sense resistor chosen should be 10 ppm/°C or better.
CURRENT,
INTERNAL
1. ZERO
2. POSITIVE
3. NEGATIVE
Internal
Output Current:
1. 0.0A
2. +Current FS
3. –Current FS
Short with Meas.
Shunt
Automatic CM
1. DVM between probe
terminals of Meas.
Shunt (LO towards COM
S)
2. Adjust for zero, posi-
tive and negative FS
CURRENT,
PROTECTION
1. POSITIVE
2. NEGATIVE
Internal
Output Current:
1. +Current FS
2. -Current FS
Short with Meas.
Shunt
Automatic VM
1. DVM between probe
terminals of Meas.
Shunt (LO towards COM
S)
2. Adjust for positive and
negative FS.
CURRENT,
EXTERNAL
1. ZERO
2. POSITIVE
External:
1. 0.0V
2. +10.0V
(Analog I/O Port
pin 11 ref to pin 10)
Output Current:
1. 0.0A
2. +Current FS
Short with Meas.
Shunt
Automatic CM
1. DVM between probe
terminals of Meas.
Shunt (LO towards COM
S).
2)Adjust for zero, pos
FS.
CURRENT,
GAIN
1. ZERO
2. POSITIVE
External:
1. 0.0V
2. +10.0V
(Analog I/O Port
pin 11 ref to pin 10)
Output Current:
1. 0.0A
2. 0.0A
Short with Meas.
Shunt
Automatic CM
1. DVM between probe
terminals of Meas.
Shunt (LO towards COM
S)
2. Adjust for zero
(both Zero and Positive)
EXTERNAL
CONTROLS,
PARALLEL
1. ZERO
2. POSITIVE
External:
1. 0.0V
2. +10.0V
(Par/Ser CTRL-IN
Port pin3 ref. to
pin1)
Output Current:
1. 0.0A
2. +Current FS
Short with Meas.
Shunt
Automatic CM
1. DVM between probe
terminals of Meas.
Shunt (LO towards COM
S)
2. Adjust for zero, pos.
FS
3. Calibrate unit for
Slave in Parallel
EXTERNAL
CONTROLS,
I_OUT
1. ZERO
2. POSITIVE
INTERNAL
Voltage at Par/Ser
CTRL-IN Port pin 6
ref. to pin1:
1. 0.0V
2. +10.0V
Short with Meas.
Shunt
Automatic CM
1. DVM at Par/Ser
CTRL-IN Port pin 6 ref.
to pin 1
2. Adjust for zero,
+10.0V
3. Calibrate unit for Mas-
ter in Parallel
EXTERNAL
PROTECTION,
Pos. Voltage
Neg. Voltage
Pos. Current
Neg. Current
(together)
1. ZERO
2. FULL SCALE
External:
1. 0.0V
2. +10.0V
(Analog I/O Port
pins 14, 6, 13, 5 ref
to pin12)
N/A
No requirements
Automatic internal
measurement
TABLE 4-1. CALIBRATION SUMMARY (CONTINUED)
Type
Step
Reference Type and
Value
Monitored Parameter
Output Conditions
Notes
Содержание BOP-MG 1KW
Страница 2: ......
Страница 10: ......
Страница 20: ...x BOP 1K 111315 FIGURE 1 1 HIGH POWER BOP SERIES POWER SUPPLY...
Страница 39: ...BOP HIPWR 111315 1 19 1 20 Blank FIGURE 1 3 BOP OUTPUT CHARACTERISTICS...
Страница 40: ......
Страница 56: ...2 16 BOP HIPWR 111315 FIGURE 2 5 PARALLEL CONFIGURATION LOCAL SENSING TYPICAL...
Страница 57: ...BOP HIPWR 111315 2 17 FIGURE 2 6 PARALLEL CONFIGURATION REMOTE SENSING TYPICAL...
Страница 68: ......